...
Supported Models
eSITEeSiteCommunication Method
XXXXXXX
ETHERNET/SNMP
RS485 (This connection method is not recommended, but if necessary, contact Galooli support)Read/Write Community
Read - public
Write - esitex10Network configuration
Device IP |
---|
192.168.20.10 |
---|
Subnet mask |
255.255.255.0 |
Gateway |
192.168.20.1 |
Host IP (Web/Elara configuration) |
Device Configuration
...
192.168.20.11 |
Device Configuration
To be announced
Supported Parameters (SNMP)
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Total_Output_KWH | Rectifier_X.Total Load Energy [KWH] |
|
Voltage | Rectifier_X.U_System [V] | |
Current | Rectifier_X.I_Load | |
Battery_Current | Rectifier_X.I_Battery | |
Battery_SOC_Percentage | Rectifier_X.State_Of_Charge | |
Battery_Temperature | Rectifier_X.Temperature_Battery [Celsius] | |
Solar_W | Rectifier_X.Solar_Power [W] | |
Solar_KWH | Rectifier_X.Solar_Total_Power [KWH] | |
Rectifier_Current | Rectifier_X.I_Rectifier |
|
Temperature_Ambient | Rectifier_X.Temperature_Ambient [Celsius] |
|
Solar_1-6_Voltage | Rectifier_X.Solar_Voltage_X [V] |
|
Solar_1-6_Current | Rectifier_X.Solar_Current_X [A] | |
Grid_Voltage_Phase_1-3 | TBA |
|
DG_Signal | Rectifier_X.Generator Signal |
|
Communicating_Modules | Rectifier_X.Communication_Rectifier_Modules |
|
Communicating_Solar_Modules | Rectifier_X.Communication_Solar_Modules |
|