Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

After you have configured the ID of the device, you can now connect the DC meter directly to the Elara unit as described in the DC Meter CE11 Installations document.

  1. Re-open Power Center.

    Image Modified
  2. Open the “Active Device” dropdown and select “Elara.”

    Image Modified
  3. Open the “Connect Via” dropdown and select the relevant “COM port”.

  4. Navigate to the “Elara” tab.

    Image Modified
  5. Navigate to the “Configuration” tab and click “Read all parameters” under the Elara device.

    Image Modified
  6. Click the “Add Port-1 Device”.

    Image Modified
  7. Select relevant device information according to the previous configurations.

...

  1. (warning) Pay attention to the model of the CE Transducer CE11 device. For example:

    image-20240122-143731.pngImage Added

...

ID 1-5 - Batteries meter

ID 34 - Solar meter

ID 60-69 - Tenants 1-10 

ID 90-99 - Tenants 11-20

8. Click the “Write All Parameters” button to save the changes and reset the unit.

...

  1. Return to the “Configuration” tab and confirm that the DC meter setup was registered.

    Image Modified