Field Name

Field Description

Generator X Total Manual Mode Hours

The total hours the generator spent in manual mode over the period selected. Here is how the calculation is performed:

  • There must be a minimum of 15 minutes between the last broadcast and the current broadcast, unless it is a SWAN gateway, in which case it must be a maximum of 75 minutes.

  • Generator_X.Running = True AND Generator_X.Working Mode = Manual

Generator X Initial Engine Hours

The first/ last record of the engine hour value for the selected time range. 
Based on the field Site_Global.DGX_Engine_Hours.

Data aggregation should be performed on the fields on a daily basis.

Generator X Final Engine Hours

Generator X Total Engine Hours

The total hours the engine was running in the selected time range. Based on the field Site_Global.DGX_Engine_Hours.

Data aggregation should be performed on the fields on a daily basis

Generator X Overall [Liter/H]

The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (including drops) and the engine hours.

Generator X Overall Fuel [Liter]

The total amount of fuel consumed (including fuel drops) in the selected time range.

Generator X Fuel Sensor Operational Consumption [Liter/H]

The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (not including drops) and the engine hours.

Generator X Operational Fuel [Liter]

The total amount of fuel consumed (not including fuel drops) in the selected time range.

Generator X Fuel Drops

Number of fuel drops in the selected time range.

(warning) In order to collect this data, a fuel drop event must be created - Fuel Events*

Generator X Total Fuel Drop [Liter]

The total amount of fuel that was lost as a result of fuel drops.

(warning) In order to collect this data, a fuel drop event must be created - Fuel Events*

Generator X Refuels

Number of refuels in the selected time range.

Generator X Total Refueled [Liter]

The total amount of fuel that was refueled in the selected time range.

Generator X Ignition Count

Number of generator ignitions during the selected time range.

Generator X Initial Fuel [Liter]

The fuel level of the generator in the first/last record in the selected time range.

Generator X Final Fuel [Liter]

Generator X Minimum Fuel Level [Liter]

The minimum fuel level value of the generator in the selected time range.

Generator X Frequency Max [Hz]

The minimum and a maximum frequency of the generator in the selected time range.

Generator X Frequency Min [Hz]

Generator X Battery Voltage Max [V]

The minimum and a maximum voltage of the generator's battery in the selected time range.

Generator X Battery Voltage Min [V]

Generator X Oil Pressure Max, Min, Avg* [kPa]

The minimum, maximum and average oil pressure of the generator in the selected time range.

Generator X Total Flow Meter Fuel [Volume]

Fuel consumption from a dedicated sensor (Flow Meter) on a daily basis.

Generator X Average Flow Rate [Volume\Hour]

The daily average of fuel that passed through the sensor (Flow Meter per hour.



Generator X - Load Based Fuel ConsumptionGalooli Operational Consumption [Liter/H]

Whenever there's an illogical result in the system sensor fuel consumption parameters reading (Generator X Operational X Fuel Sensor Operational Consumption [Liter/H]), the CPH field will show an estimated assessment of the fuel consumption based on the following:

  1. Final and initial fuel levels considering drops and refuels.

  2. Fuel consumption patterns of the generator.

  3. Estimated consumption based on

the
  1. generator's load and the KVA

Generator KVA must be configured below the additional info.

Logic:

Use the value of the parameter "Generator X Operational

https://galooli.atlassian.net/wiki/spaces/KP/pages/2830041108/Information#Additional-Information

Generator X Load Based Consumption [Liter/H]

" if it doesn't out of the valid range (Based on internal valid ranges CPH table)

If "Generator X Operational Consumption [Liter/H]" values are out of this range, than use the calculation Y=CPH Result, X = Generator Load [%]:

Generator Load

Provide the estimated fuel consumption tailored to the generator's specific KVA, calculated based on the generator's load.

Generator load [%] = (Generator1/2 Load Power - Avg [kW])/(0.8 * Additional info → Generator.Generator1/2.KVA)

Generator KVA must be configured below the additional info.

https://galooli.atlassian.net/wiki/spaces/KP/pages/2830041108/Information#Additional-Information

*Zeros are ignored in the calculation of averaged fields