Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

A Ultragate device connects to all sensors, accessories, and devices, gathering data and sending it to the Galooli platform/servers.

...

Model

Galooli PN.

EG818

100-RTUSRULT-020

Table of Contents

...

Operating System

Ubuntu 2

Processor

Quad-core ARM Cortex-A55 64bit CPU, up to 2.0GHz,RK3568

RAM

DDR4 4GB

Memory

eMMC 16GB is the default memory. A 32GB is optional.

NPU

1TOPS NPU, Support Caffe/Mxnet/TensorFlow/TF Lite/ONNX/Darknet models



Network Interface

Dual 10/100 Ethernet ports

2.4GHz/5.8GHz Wi-Fi 802.11b/g/n/ac (Optional)

4G mobile network

Bluetooth (Optional)

Defaulted IP:

  • ETH 0 Port 1: 192.168.1.11

  • ETH 1 Port 2: 192.168.100.55

SIM

1*SIM slot Nano-SIM(4FF)


LTE Frequency Bands

LTE-FDD B1/3/5/7/8/20
LTE-TDD B38/40/41
WCDMA B1/5/8
GSM/EDGE B3/8




GNSS

GPS, GLONASS, BDS, Galileo and QZSS
Protocol: NMEA 0183
Data update rate: 1 Hz by default
Sensitivity:
Acquisition Autonomous -146 dBm
Tracking Autonomous -157 dBm
Accuracy: Autonomous @ open sky 2.5

Display

1*HDMI OUT 2.0 ,4K 60fps

RTC

Built-in real-time clock battery, supports scheduled power on/off.


USB

1*USB3.0 HOST
1*USB3.0OTG


LED Indicators

WORK When the device is working properly, it blinks for 1s frequency
POW on when the gateway is powered up
DI n - on when the channel is activated by input signal
DO n - on when the channel output is activated

Can bus

1 CAN2.0 as default. CANFD is optional.

Button

1*upgrade for OTA, REC

Serial Ports

2*RS232 ,2*RS485

EMC level: IEC61000-4-2ESD, Level 2, class B, contact 4KV, air4 KV

Serial Signals

RS-232 5V/3.3V(output), TxD, RxD, GND
RS-485 5V/3.3V(output),A,B, GND



IO Interfaces

4 DI: dry/wet contact
DI voltage range 0-36V (Max. 36V), High 5-36V, Low 0-2V
2 DO: Relay
DO Max. 10A-277VAC/28VDC for NO,5A-250VAC for NC
4 AI: Voltage range 0-15v (Max.18V); Analog input Current range 4~20mA (Max. 40mA)
EMC level: IEC61000-4-2, Level 2, class B, contact 4KV, air 4KV


Power Supply

DC12V/2A
Connector: Jack Barrel Type DC5.5*2.1mm Round socket or 2 PIN terminal block
EMC level: IEC61000-4-2, Level 2, class B, contact 4KV, air 4KV

Operating Temperature

-10 - 70°C

Storage Temperature

-20 - 85  °C

Humidity

5% - 80%

Dimension

210mm*106mm*50mm

Installation

Panel mounting, DIN-Rail mounting



International Protection (IP Code)

IP30.

  • If the Gateway is installed in a Galooli cabinet tray and the tray is inserted into a communication cabinet, then the IP Code is determined by the specific communication cabinet being used.

  • When the Gateway is inserted into Galooli's Metal Box Set, it will have IP codes corresponding to the Metal Box Sets - IP65


Certificate

CE

RoHS (in progress)

...

Front - from left to right

Top Side

Pin#

Name

Description

Type

1

V1+

Voltage1 +

Analog

Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#57D9A3

In order to connect the Ultragate analog inputs to the Galooli Tray/Metal box inputs, the connections should be made in the following order:

Ultragate V > Tray U-AN

Ultragate COM > Tray GND

2

I1+

Current1 +

3

Com1

N/A

4

V2+

Voltage2 +

5

I2+

Current2 +

6

Com2

N/A

7

V3+

Voltage3 +

8

I3+

Current3 +

9

Com3

N/A

10

V4+

Voltage4 +

11

I4+

Current4 +

12

Com4

N/A

13

V+

Voltage +

Digital

Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#57D9A3

In order to connect the Ultragate digital inputs to the Galooli Tray/Metal box inputs, the connections should be made in the following order:

Ultragate D > Tray U-D

Ultragate COM > Tray GND

14

V-

Voltage -

15

D1

Digital 1

16

Com1

N/A

17

D2

Digital 2

18

Com2

N/A

19

D3

Digital 3

20

Com3

N/A

21

D4

Digital 4

22

Com4

N/A

Bottom Side

Pin#

Name

23

DC 12V/2A

24

HDMI

25

AUD

26

ETH 0

27

ETH 1

28-29

2 - USB 3.0

30-31

2 - RS485

image-20240916-121509.pngImage Removed
image-20240916-121509.pngImage Added

32-33

2 RS232

34

GSM

35

GPS

36

SIM

Back - from left to right

...