Field Name | Field Description | |
---|---|---|
Generator X Total Manual Mode Hours | The total hours the generator spent in manual mode over the period selected. Here is how the calculation is performed:
| |
Generator X Initial Engine Hours | The first/ last record of the engine hour value for the selected time range. Data aggregation should be performed on the fields on a daily basis. | |
Generator X Final Engine Hours | ||
Generator X Total Engine Hours | The total hours the engine was running in the selected time range. Based on the field Site_Global.DGX_Engine_Hours. Data aggregation should be performed on the fields on a daily basis | |
Generator X Overall [Liter/H] | The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (including drops) and the engine hours. | |
Generator X Overall Fuel [Liter] | The total amount of fuel consumed (including fuel drops) in the selected time range. | |
Generator X Fuel Sensor Operational Consumption [Liter/H] | The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (not including drops) and the engine hours. | |
Generator X Operational Fuel [Liter] | The total amount of fuel consumed (not including fuel drops) in the selected time range. | |
Generator X Fuel Drops | Number of fuel drops in the selected time range. In order to collect this data, a fuel drop event must be created - Fuel Events* | |
Generator X Total Fuel Drop [Liter] | The total amount of fuel that was lost as a result of fuel drops. In order to collect this data, a fuel drop event must be created - Fuel Events* | |
Generator X Refuels | Number of refuels in the selected time range. | |
Generator X Total Refueled [Liter] | The total amount of fuel that was refueled in the selected time range. | |
Generator X Ignition Count | Number of generator ignitions during the selected time range. | |
Generator X Initial Fuel [Liter] | The fuel level of the generator in the first/last record in the selected time range. | |
Generator X Final Fuel [Liter] | ||
Generator X Minimum Fuel Level [Liter] | The minimum fuel level value of the generator in the selected time range. | |
Generator X Frequency Max [Hz] | The minimum and a maximum frequency of the generator in the selected time range. | |
Generator X Frequency Min [Hz] | ||
Generator X Battery Voltage Max [V] | The minimum and a maximum voltage of the generator's battery in the selected time range. | |
Generator X Battery Voltage Min [V] | ||
Generator X Oil Pressure Max, Min, Avg* [kPa] | The minimum, maximum and average oil pressure of the generator in the selected time range. | |
Generator X Total Flow Meter Fuel [Volume] | Fuel consumption from a dedicated sensor (Flow Meter) on a daily basis. | |
Generator X Average Flow Rate [Volume\Hour] | The daily average of fuel that passed through the sensor (Flow Meter per hour. | |
|
- Galooli Operational Consumption [Liter/H |
] | Whenever there's an illogical result in the |
sensor fuel consumption |
reading (Generator |
X Fuel Sensor Operational Consumption [Liter/H]), the |
field will show an |
assessment of the fuel consumption based on the following:
|
| Generator KVA must be configured below the additional info. |
Logic:
Use the value of the parameter "Generator X Operationalhttps://galooli.atlassian.net/wiki/spaces/KP/pages/2830041108/Information#Additional-Information |
Generator X Load Based Consumption [Liter/H] |
If "Generator X Operational Consumption [Liter/H]" values are out of this range, than use the calculation Y=CPH Result, X = Generator Load [%]:
Generator Load
Provide the estimated fuel consumption tailored to the generator's specific KVA, calculated based on the generator's load. Generator load [%] = (Generator1/2 Load Power - Avg [kW])/(0.8 * Additional info → Generator.Generator1/2.KVA) |
*Zeros are ignored in the calculation of averaged fields