If there is a rectifier on site, then it is recommended that the Elara is connected and configured to the rectifier
...
before the installation and configuration of the battery cell monitoring unit
Download the Battery Monitoring Software (PBMS2000 Monitoring Software)
...
Rectifier IP | Elara IP | Battery cell monitoring hub IP |
---|---|---|
192.168.100.100 | 192.168.100.101 | 192.168.100.102 |
...
9. Go to “Balance Setting”, and click "Yes" in the "Balance Enable" row. Afterward, write down 98.0 at the "Target Balance (%)" and 120 at the "Balance Interval Time (s)”. Save the configurations.
...
10. In the "Alarm Setting", click on "Recommend". A new window will open, click on "Confirm" and go back to the previous window. Click "Save”.
...
Make sure that the recommended settings are appropriate for your batteries
...
11. Click on "Res Measuring" and follow the instructions below.
...
1112. Click on “Address Info” and then “Save”
...
1213. confirm that all modules are communicating with data, close the “Settings” window, and press the “Read” button.
...
On “Discharge” status it provides a negative value.
When the status is “Floating” or “Rest” status the system will provide a value of 0 (A).
...