If the hardware in question supports one of the common communication protocols that Galooli supports, the customer can complete the entire process integration independently and get the raw datastart collecting supported parameters.

On the other hand, if the following parameters are required, Galooli's involvement is necessary:

...

New Device Name

...

Default Settings in the Power Center

In case one of the following is required as part of the integration, Galooli will have to be included in the integration process:

  • Device name to show in the system display.

  • Get the new integration as one of the power center defaults.

  • New parameters that are not supported by Galooli.

  • Device Alarms

  • X-Ray Parameters

In such cases, the data review and decision regarding whether to proceed with the integration are made by Galooli. This decision is a commercial one and depends on the required effort and the quantity of units involved. If this applies to your case, please contact your designated Galooli representative in advance.

...

customer will submit the integration request to his account manager in Galooli.

Galooli will analyze the integration request and reply to the customer if the request is accepted.

Table of Contents
minLevel1
maxLevel6
outlinefalse
styledefault
typelist
printabletrue

Pre Integration Required Data

...

The configuration process varies depending on the protocol type. Below, we will provide details about the different types of protocols and the way to configure the devices.

  1. Ensure that the new device is connected to the gateway and the gateway is connected to your computer.

  2. Download the Galooli Power Center platform and login

  3. Configure the new device in the Power Center . Depending on the device communication method/protocol, select the appropriate method of adding the device to the Power Centeraccording to the below:

Modbus & Modbus over TCP Protocols

  • For the Modbus & Modbus over TCP Protocols, add a serial device (Modbus) or Modbus ETH (Modbus over TCP) and then select the appropriate device.

  • For “Modbus” update the Physical Device ID, Virtual Device ID, Device Baudrate as needed.
    For “Modbus over TCP” update the Physical Device ID, Virtual Device ID, and Device IP and the Device Port as needed.

  • Finally, click Apply to save the changes.

Modbus

Modbus over TCP

image-20241128-124002.pngimage-20241128-121552.png
  • Navigate to the Configuration tab, double-click on the existing device, select the ID line, and then click Add Item.

...

  • The wizard will guide you through selecting the Assignment and configuring its parameters.

    Add the first assignment, complete the parameters using the device's technical specification manual, and click Apply to save the changes.

...

...

The wizard will guide you through selecting the Assignment and configuring its parameters.

Add the first assignment, complete the parameters using the device's technical specification manual, and click Apply to save the changes.

“SNMP” Protocol

  • For the SNMP protocol, add the “SNMP ETH” device and then select the appropriate device. Update the Device ID and the Virtual Device ID as needed.

  • Finally, click Apply to save the changes.

...

  • Navigate to the Configuration tab, double-click on the existing device, select the ID line, and then click Add Item.

...

  • The wizard will guide you through selecting the Assignment and configuring its parameters.

...

  • Add the first assignment, complete the parameters using the device's technical specification manual, and click Apply to save the changes.

...

The next steps apply equally to all protocols.

  • Click "Write configuration", wait until the process is complete, and then click "Reset".

...

  • Click on the "Status" tab, open the relevant device option, and compare the Power Center value of the assignment you added in the previous step with the actual value. Thus, you will be able to verify the accuracy of the readings in Power Center.

...

  • Repeat the process for each assignment separately. After each new assignment is added, be sure to click "Write configuration", wait until the process has been completed, and then click "Reset". For each new assignment , make sure to verify the receiving of data each time.

  • Ensure that all relevant alarms are listed, as well as any remote control parameters. The technical specifications/datasheet of the product contains all the relevant information. You may need to contact the manufacturer if necessary. Apply the changes to complete the process.

  • Click "Write configuration", wait until the process is complete, and then click "Reset".