Field Name | Field Description | Calculation Method |
---|---|---|
Tenant X Initial [KWH] | The first record of the kWh value that was read from the tenant's meter, for the selected time range. |
|
Tenant_ |
X.Total_KWH [KWH] | |
Tenant X Final [KWH] | The last record of the kWh value that was read from the tenant's meter, for the selected time range. |
Tenant X Total [KWH] | The total energy consumption (kWh) of the tenant, is based on the readings from the tenant's meter. When the difference between two records exceeds 7500kWh, the system will not sum the difference because it is too large. |
Tenant X Total |
Generator [KWH] | The total energy consumption (kWh) of the tenant that was received from the generator, is based on the readings from the tenant's meter. | Based on the field |
Tenant_X.Total_ |
Generator_KWH [KWH] |
|
Generator [KWH] | The total energy consumption (kWh) of the tenant that was not received from the generator, is based on the readings from the tenant's meter. | Based on the fields |
Tenant_ |
X.Total_KWH [KWH], |
|
X.Total_ |
Generator_KWH [KWH] | ||
Tenant X Assignment | The assignment (name) of tenant X. | |
Tenant X Min/Max/Avg* Current [A] | The minimum, maximum and average current of the tenant's meter. | |
Tenant X Min/Max/Avg* Voltage [V] | The minimum, maximum, and average voltage of the tenant's meter. | |
| The total time in the day (hours) the tenant's "Power Down" alarm was false, meaning the tenant received voltage. | Based on records where |
Tenant_X_Alarm_Power_Down = No. | ||
| The total time in the day (hours) the tenant's "Load Down" alarm was false, meaning the tenant received current. | |
| The calculated energy consumption (kWh) of the tenant, is based on voltage and the current provided to the tenant. | Based on the fields |
Tenant_X.V_LY [V], |
Tenant_ |
X.I_LY [V] X=1->20, Y=1->3 | ||
Tenant X Min/Max/Avg* Power | The minimum, maximum, and average power of the tenant's meter. | |
| As of the date the report was run, this field shows the tenants registered for the unit.
|
The availability time is calculated by accumulating the time between records where the relevant asset was connected. The time will be reserved only if the time difference between the subsequent records is less than 15 * minutes. In addition, if the calculated availability value is larger than the Data Availability value, the value will be assigned with to the Data Availability value.
*Zeros are ignored in the calculation of averaged fields