Field Name

Field Meaning and Logic


Generator_X.Engine_Hours_Tampering

The digital field becomes "True" when the difference in engine hours exceeds the difference in records by more than two hours.
[2 < (ABS(engine hours difference - time difference].

Rectifier_X.Alarm_Surppressed

It is an alarm from the rectifier that indicates that other alarms have been configured not to be active, leading to alerts not being received by the user.

Site_Global.Alarm Galooli Generator X High Load

Site_Global.Alarm Galooli Generator X Very High Load

Site_Global.Alarm Galooli High Battery Current

The alarm will be activated if the unit is set to "Global DC.High Battery Current Threshold" AND "Site_Global.Battery_Current [A] > Global DC.High Battery Current Threshold"

Site_Global.Alarm Galooli High System Voltage

The alarm will be activated if the unit is set to “Global DC.High System Voltage Threshold” AND “Site_Global.U_System [V] > Global DC.High System Voltage Threshold”


Rectifier_X.Alarm Internal Solar SPD Fail

This alarm is displayed when there is an (internal) fault in the 'lightning protection' mechanism (which keeps electrical devices from being damaged by high current surges like lightning). In this case, it is the entry of diesel current into the rectifier. For Eltek smartpack 2 touch rectifiers only.