Communication Troubleshooting

How to Detect the Fault?

Fault Description

Troubleshooting Steps

The AC meter

Polarium battery connection state is

“No Connection”Image Removed

Elara connected but the AC meter displayed “No connection”

  1. The AC meter's LEDs should be blinking and the power supply should be on.

    Image Removed
  2. Check that RS485 A and RS485 B cables are connected correctly (RS485 A = pin 14, RS485 B = pin 15).

    Image Removed
  3. Ensure the communication cables (RS-485) is in good condition and not broken or overly long (up to 15 meters).

  4. Make sure the baud rate of the meter is 19200 and the device ID is according to your wiring diagram.

    Image Removed

  5. Verify that Port 1 on the Elara is “host”.

    Image Removed

...

How to Detect the Fault?

...

Fault Description

...

Troubleshooting Steps

The Current & Power factors are negative

...

...

  1. As shown in the picture below, make sure the phase direction is correct

    Image Removed

...

How to Detect the Fault?

Fault Description

Troubleshooting Steps

The voltage reading is higher than allowed
Image RemovedThe phases cables of the AC ring connected to the wrong pins in the AC meterVerify you connect the cables from the CT ring to the AC meter according to the relevant phases.
Pin 4 > Phase 1 Current [+] > Red cable
Pin 5 > Phase 1 Current [-] > Black cable
Pin 6 > Phase 2 Current [+] > Red cable
Pin 7 > Phase 2 Current [-] > Black cable
Pin 8 > Phase 3 Current [+] > Red cable
Pin 9 > Phase 3 Current [-] > Black cable
Image Removed

"No Connection", even though the battery is connected.

Image Added

Verify that the baud rate of the Polarium is the same as the baud rate of all devices and the Elara gateway.

Image Added

View file
namePolarium battery training.pdf