Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

In certain instances, customers express their interest in seamlessly integrating a new device into the Galooli's systems, aiming to establish it as a standard component. This integration journey is a collaborative effort between the client and Galooli. Emphasizing the importance of precision, our joint efforts are dedicated to ensuring the seamless functionality and synchronization of the product device with Galooli systems , by following to the detailed instructions outlined provided in this document.

במידה ונדרשת חומרה שהוא אחת מפרוטוקולי התקשרות הנפוצים שאנחנו תומכים אז הלקוח יכול לבצע את כל הפעולה באופן עצמאי ללא תלות בגלולי למעט ההתראות.

  • שם במערכת

  • דיפולטים בפאוור סנטר

  • לקבל התראות

  • XRAY

אלא פעולה שצריך את גלולי

בדיקת נתונים והחלטה האם לעשות אינטגרציה או לא.

...

לטובת קבלת פרמטרים חיים אפשר לקבל ללא גלולי

If the hardware in question supports one of the common communication protocols that Galooli supports, the customer can complete the entire process independently and get the raw data.

On the other hand, if the following parameters are required, Galooli's involvement is necessary:

  • New Device Name

  • Default Settings in the Power Center

  • Alarms

  • X-Ray Parameters

In such cases, the data review and decision regarding whether to proceed with the integration are made by Galooli. This decision is a commercial one and depends on the required effort and the quantity of units involved. If this applies to your case, please contact your designated Galooli representative in advance.

Table of Contents
stylenone

...

Pre Integration Required Data

TBAIf the hardware in question supports one of the common communication protocols that Galooli supports like, RS485, Ethernet, Modbus, Modbus over TCP, SNMP, please gather the following data:

  • Device Type (rectifier, generator e.g. Rectifier, Generator panel, etc.)

  • Brand - דוגמאModel - דוגמא(e.g. Delta, Eltek, DSE, Cummins)

  • Model (e.g. Orion, SmartPack, DSE 7320, PCC1302)

  • Technical Manual: A detailed guide for the specific model is required to understand how to configure the device for integration with our system.

  • Communication Protocol/MIB File: Depending on the integration type, ensure the appropriate files are available.

  • Register/OID List vs. Existing System Fields: Provide a clear mapping of registers or OIDs to the fields already present in our system. If needed, please reach out to your Galooli contact person.

    • Include scaling factors (if applicable).

    • Alarms list

    • List parameters needed for X-Ray depending on the integration type.

    • אם יש צורך יש לפנות לאיש הקשר בגלולי

    • This checklist This section is also applicable for requests to update an existing integration. In such cases, all items remain valid except for providing documentation, which should already exist from the initial integration phase.

...

Configuration Process

Galooli currently supports the following communication methods and protocols:

  • RS485, Ethernet

  • Modbus, MכלAodbus over TCP, SNMP

In case your hardware product supports the communication methods and protocols listed above continue to paragraph 1

Note

In the event that the communication method or protocol is different from those described above, please open a support ticket with Galooli. Upon receiving an answer from Galooli, you may proceed with the process.

...

  1. Ensure that the new device is connected to your computer.

  2. According to the product protocol, the following steps should be taken:

    • Modbus” protocol - The Physical Device ID should be configured using the manual guideline that came with the device. Keep a record of the Physical Device ID so you can use it later.

    • Modbus over TCP” protocol - The Device IP address should be configured within the same range as this of the Galooli gateway using the manual instructions provided with the device. For example Elara IP is 192.168.100.101 by default. Keep a record of the Device IP Address so you can use it later.

    • SNMP” protocol - The Device IP address should be configured within the same range as this of the Galooli gateway using the manual instructions provided with the device. For example Elara IP is 192.168.100.101 by default. Keep a record of the Device IP Address so you can use it later.

  3. Disconnect the device from the computer.

  4. Download the Galooli Power Center platform.

  5. Assemble the Elara gateway and connect it to a power source and your computer.

  6. Connect the the new device to the Elara gateway.

  7. Open the Power Center and make a serial connection to the Elara gateway.

  8. Configure the new device in the Power Center:

...