In certain instances, customers express their interest in seamlessly integrating a new hardware product device into the Galooli systems, aiming to establish it as a standard component. This integration journey is a collaborative effort between the client and Galooli. Emphasizing the importance of precision, our joint efforts are dedicated to ensuring the seamless functionality and synchronization of the product with Galooli systems, following the detailed instructions outlined in this document.
במידה ונדרשת חומרה שהוא אחת מפרוטוקולי התקשרות הנפוצים שאנחנו תומכים אז הלקוח יכול לבצע את כל הפעולה באופן עצמאי ללא תלות בגלולי למעט ההתראות.
שם במערכת
דיפולטים בפאוור סנטר
לקבל התראות
XRAY
אלא פעולה שצריך את גלולי
בדיקת נתונים והחלטה האם לעשות אינטגרציה או לא.
ההחלטה תלויה במאמץ ובכמויות. החלטה מסחרית
לטובת קבלת פרמטרים חיים אפשר לקבל ללא גלולי
Table of Contents | ||
---|---|---|
|
Step 1 - Pre Integration Required Data
...
TBA
Device Type (e.g., rectifier, generator panel, etc.)
Brand - דוגמא
Model - דוגמא
Technical Manual: A detailed guide for the specific model is required to understand how to configure the device for integration with our system.
Communication Protocol/MIB File: Depending on the integration type, ensure the appropriate files are available for compatibility.
Register/OID List vs. Existing System Fields: Provide a clear mapping of registers or OIDs to the fields already present in our system.
Include scaling factors (if applicable).
Alarms list
List parameters needed for X-Ray depending on the integration type.
אם יש צורך יש לפנות לאיש הקשר בגלולי
This checklist is also applicable for requests to update an existing integration. In such cases, all items remain valid except for providing documentation, which should already exist from the initial integration phase.
Step 2 -
...
TBA
Step 3 - Self Integration
...
Configuration
Galooli currently supports the following communication methods and protocols:
RS485, Ethernet
Modbus, Modbus MכלAodbus over TCP, SNMP
In case your hardware product supports the communication methods and protocols listed bellow above continue to step paragraph 1.
Note |
---|
In the event that the communication method or protocol is different from those described above, please open a support ticket with Galooli. Upon receiving an answer from Galooli, you may proceed with the process. |
Please ensure that the Galooli gateway and the new device are in the office.
Ensure that the new device is connected to your computer.
According to the product protocol, the following steps should be taken:
“Modbus” protocol - The Physical Device ID should be configured using the manual guideline that came with the device. Keep a record of the Physical Device ID so you can use it later.
“Modbus over TCP” protocol - The Device IP address should be configured within the same range as this of the Galooli gateway using the manual instructions provided with the device. For example Elara IP is 192.168.100.101 by default. Keep a record of the Device IP Address so you can use it later.
“SNMP” protocol - The Device IP address should be configured within the same range as this of the Galooli gateway using the manual instructions provided with the device. For example Elara IP is 192.168.100.101 by default. Keep a record of the Device IP Address so you can use it later.
Disconnect the device from the computer.
Download the Galooli Power Center platform.
Assemble the Elara gateway and connect it to a power source and your computer.
Connect the the new device to the Elara gateway.
Open the Power Center and make a serial connection to the Elara gateway.
Configure the new device in the Power Center:
...
Choose the "Configuration" tab, double click on the existing device, click on the “Port” line and click on “Add item”.
The following wizard will allow you to choose the “Assignment” and specify the different parameters for that assignment. Listed below are Galooli's recommendations for the required assignments.
Add the first assignment, fill in the parameters using the technical specification manual that came with the device, and apply the changes.Click "Write configuration", wait until the process is complete, and then click "Reset".
...
Modbus | Modbus Over TCP | SNMP |
---|---|---|
Engine_Hours | Battery_Voltage | Total_Output_KWH |
Grid_Voltage_Phase_1/2/3 | Battery_Current | Solar_KWH |
Battery_Voltage | Battery_SOC_Percentage | Solar_W |
Engine_Speed | Balancing_Percentage | Voltage |
Frequency | Status | Current |
Voltage_Phase_1/2/3 | Cells_Count | Battery_Current |
Current_Phase_1/2/3 | Internal_Resistance | Battery_SOC_Percentage |
Coolant_Temperature | Temperature_1 | Battery_Temperature |
Oil_Pressure | Cells_Group_1 | Solar_X_Voltage |
Working_Mode | Solar_X_Current | |
Total_Output_KWH | Rectifier_Current |
להפנות את הלקוח לקישורים של השמות של השדות בפאוור