Updated Generator Criticality
We updated the criticality level for the generator alarms based on the following table:
Item | Previous Version | Current Version |
---|---|---|
Generator_1.low_oil_pressure | Critical | Critical |
Generator_1.Emergency_stop | Critical | Critical |
Generator_1.Low_coolant | Urgent | Observation |
Generator_1.High_coolant | Urgent | Urgent |
Generator_1.Over_speed | Observation | Urgent |
Generator_1.Under_speed | Observation | Urgent |
Generator_1.Over_frequency | Observation | Urgent |
Generator_1.Under_frequency | Observation | Urgent |
Generator_1.High_voltage | Observation | Urgent |
Generator_1.low_voltage | Observation | Urgent |
Generator_1.Battery_high | Observation | Urgent |
Generator_1.Battery_low | Urgent | Urgent |
Generator_1.Charge_alternator_fail | Observation | Urgent |
Generator_1.Fail_to_close | Observation | Observation |
Generator_1.Fail_to_stop | Observation | Observation |
Generator_1.Not_in_AutoMode | Urgent | Urgent |
Generator_1.Door_Open | Observation | Observation |