  • The fuel level, load, and world mode are the same as in the main view.

  • Control button - clicking the control will open a drop-down with the options - :

    • Engine Start, Engine Stop

    ,
    • - Use the generator control panel to start and stop the generator

    • Auto Mode, Stop Mode, Manual Mode

    ,
    • Test On Load Mode

    • Alarms Reset, and Alarms Reset 2

    • Output - On,

    and Alarms Reset2 (see picture below).
    • Output - Off - Use the relay and Elara gateway to start and stop the generator

After clicking one of the options, a confirmation message will appear as a popup. "Are you sure? The selected command will be applied to the generator".

...

     

    • Engine Hours - Generator_1.Engine_Hours

    • Coolant Temp (Generator_1.Coolant Temp)

      • Color based on Generator1.High_Coolant (Urgent-Orange), Low_Coolant (Non-Urgent-Yellow)

    • Battery Level (Generator_1.Battery_Level)

      • Color if Generator1.Battery_High Or Generator_1.Battery_Low (Urgent-Orange)

    • Oil Pressure - (Generator_1.Oil Pressure)

      • Color based on Generator1.Low_oil_pressure (Critical-Red)

    • Engine Speed - (Generator_1.Engine Speed)

      • Color based on Generator_1.Over_Speed, Generator_1.Under_Speed (Urgent-Orange)

    • Frequency (Generator_1.Gen_Frequency)

      • Color based on Generator1.Frequency_High, Generator1.Frequency_Low (Urgent-Orange)

    • Phase 1 - Voltage, Current (Generator_1.Gen_V1, Gen_I1)

      • Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Output High Voltage Threshold. 

      • Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Output Minimal Voltage Threshold

    • Phase 2 - Voltage, Current (Generator_1.Gen_V2, Gen_I2)

      • Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Output High Voltage Threshold. . 

      • Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Output Minimal Voltage Threshold

    • Phase 3 - Voltage, Current (Generator_1.Gen_V3, Gen_I3)

      • Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Output High Voltage Threshold. . 

      • Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Output Minimal Voltage Threshold

    • Grid Voltage - phases 1-3 (Generator_1.Grid_V1, V2, V3). display only of site layout containing "ONGRID"

    • Alarms - display the active digitals under the group Generator_1 with color according to the severity. Include also fuel digitals from site global:

      • Fuel_1 Low

      • Fuel_1 VeryLow

      • Alarm_FuelTank_Hatch_1

      • Fuel_1 Disconnected

      • Not includes the following digitals under Generator_1 - Alarm_Active, Alarm_Critical, Alarm_Urgent, Alarm_Non_Urgent, Alarm_Indication

    ...

    Configurations->DG1_Running is true and Generator_1.Configured is false.