Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Field Name

Field Description

Generator X Initial Engine Hours


The first/ last record of the engine hour value for the selected time range. 

Based on the field Site_Global.DGX_Engine_Hours

Generator X Final Engine Hours

Generator X Total Engine Hours

The total hours the engine was running in the selected time range. Based on the field Site_Global.DGX_Engine_Hours.

Generator X Overall [Liter/H]

The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (including drops) and the engine hours.

Generator X Overall Fuel [Liter]

The total amount of fuel consumed (including fuel drops) in the selected time range.

DGenerator

Generator X Operational Consumption [Liter/H]

The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (not including drops) and the engine hours.

Generator X Operational Fuel [Liter]

The total amount of fuel consumed (not including fuel drops) in the selected time range.

Generator X Fuel Drops

Number of fuel drops in the selected time range.

Generator X Total Fuel Drop [Liter]

The total amount of fuel that was lost as a result of fuel drops.

Generator X Refuels

Number of refuels in the selected time range.

Generator X Total Refueled [Liter]

The total amount of fuel that was refueled in the selected time range.

Generator X Ignition Count

Number of generator ignitions during the selected time range.

Generator X Initial Fuel [Liter]

The fuel level of the generator in the first/last record in the selected time range.

Generator X Final Fuel [Liter]

Generator X Minimum Fuel Level [Liter]

The minimum fuel level value of the generator in the selected time range.

Generator X Frequency Max [Hz]

The minimum and a maximum frequency of the generator in the selected time range.

Generator X Frequency Min [Hz]

Generator X Battery Voltage Max [V]

The minimum and a maximum voltage of the generator's battery in the selected time range.

Generator X Battery Voltage Min [V]

Generator X Oil Pressure Max, Min, Avg* [kPa]

The minimum, maximum and average oil pressure of the generator in the selected time range.

Generator X Total Flow Meter Fuel [Volume]

Fuel consumption from a dedicated sensor (Flow Meter) on a daily basis.

Generator X Average Flow Rate [Volume\Hour]

The daily average of fuel that passed through the sensor (Flow Meter per hour.




Generator X Load based Fuel Consumption [Km/Liter]

In this field, the generator's fuel consumption is calculated in liters per hour.

When the 'standard' data for the field (Generator 1/2 Operational consumption [Liter/Hour]) exceeds the logical range, the new field calculates the estimated fuel consumption by comparing the average “LOAD” of a generator to the KVA value.

Estimated Load based consumption = A * Generator (1\2) Load Power Average [kWh] / (0.8 * Generator.generator1\2.KVA) + B

*Zeros are ignored in the calculation of averaged fields