Field Name | Field Description |
---|---|
Generator X Initial Engine Hours |
|
Generator X Final Engine Hours | |
Generator X Total Engine Hours | The total hours the engine was running in the selected time range. Based on the field Site_Global.DGX_Engine_Hours. |
Generator X Overall [Liter/H] | The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (including drops) and the engine hours. |
Generator X Overall Fuel [Liter] | The total amount of fuel consumed (including fuel drops) in the selected time range. |
Generator X Operational Consumption [Liter/H] | The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (not including drops) and the engine hours. |
Generator X Operational Fuel [Liter] | The total amount of fuel consumed (not including fuel drops) in the selected time range. |
Generator X Fuel Drops | Number of fuel drops in the selected time range. |
Generator X Total Fuel Drop [Liter] | The total amount of fuel that was lost as a result of fuel drops. |
Generator X Refuels | Number of refuels in the selected time range. |
Generator X Total Refueled [Liter] | The total amount of fuel that was refueled in the selected time range. |
Generator X Ignition Count | Number of generator ignitions during the selected time range. |
Generator X Initial Fuel [Liter] | The fuel level of the generator in the first/last record in the selected time range. |
Generator X Final Fuel [Liter] | |
Generator X Minimum Fuel Level [Liter] | The minimum fuel level value of the generator in the selected time range. |
Generator X Frequency Max [Hz] | The minimum and a maximum frequency of the generator in the selected time range. |
Generator X Frequency Min [Hz] | |
Generator X Battery Voltage Max [V] | The minimum and a maximum voltage of the generator's battery in the selected time range. |
Generator X Battery Voltage Min [V] | |
Generator X Oil Pressure Max, Min, Avg* [kPa] | The minimum, maximum and average oil pressure of the generator in the selected time range. |
Generator X Total Flow Meter Fuel [Volume] | Fuel consumption from a dedicated sensor (Flow Meter) on a daily basis. |
Generator X Average Flow Rate [Volume\Hour] | The daily average of fuel that passed through the sensor (Flow Meter per hour. |
| In this field, the generator's fuel consumption is calculated in liters per hour. When the 'standard' data for the field fuel consumption rate (Generator X Operational consumption [Liter/Hour]) exceeds the logical range, the new field calculates the estimated fuel consumption by comparing the average “LOAD” of a generator to the KVA valueestimating the fuel consumption based on the generator's load and KVA. When A and B are coefficients that change according to the generator's KVA. |
*Zeros are ignored in the calculation of averaged fields