Field Name

Field Description

DGX Generator X Initial Engine Hours


The first/ last record of the engine hour value for the selected time range. 

Based on the field Site_Global.DGX_Engine_Hours

DGX Generator X Final Engine Hours

DGX Generator X Total Engine Hours

The total hours the engine was running in the selected time range. Based on the field Site_Global.DGX_Engine_Hours.

DGX Generator X Overall [Liter/H]

The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (including drops) and the engine hours.

DGX Generator X Overall Fuel [Liter]

The total amount of fuel consumed (including fuel drops) in the selected time range.

DGX DGenerator X Operational Consumption [Liter/H]

The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (not including drops) and the engine hours.

DGX Generator X Operational Fuel [Liter]

The total amount of fuel consumed (not including fuel drops) in the selected time range.

DGX Generator X Fuel Drops

Number of fuel drops in the selected time range.

DGX Generator X Total Fuel Drop [Liter]

The total amount of fuel that was lost as a result of fuel drops.

DGX Generator X Refuels

Number of refuels in the selected time range.

DGX Generator X Total Refueled [Liter]

The total amount of fuel that was refueled in the selected time range.

DGX Generator X Ignition Count

Number of generator ignitions during the selected time range.

DGX Generator X Initial Fuel [Liter]

The fuel level of the generator in the first/last record in the selected time range.

DGX Generator X Final Fuel [Liter]

DGX Generator X Minimum Fuel Level [Liter]

The minimum fuel level value of the generator in the selected time range.

DGX Generator X Frequency Max [Hz]

The minimum and a maximum frequency of the generator in the selected time range.

DGX Generator X Frequency Min [Hz]

DGX Generator X Battery Voltage Max [V]

The minimum and a maximum voltage of the generator's battery in the selected time range.

DGX Generator X Battery Voltage Min [V]

DGX Generator X Oil Pressure Max, Min, Avg* [kPa]

The minimum, maximum and average oil pressure of the generator in the selected time range.

Generator X Total Flow Meter Fuel [Volume]

Fuel consumption from a dedicated sensor (Flow Meter) on a daily basis.

Generator X Average Flow Rate [Volume\Hour]

The daily average of fuel that passed through the sensor (Flow Meter per hour.

*Zeros are ignored in the calculation of averaged fields