In the event that a preliminary configuration process between Elara and the rectifier has already been completed, proceed to step 1the “Adding Modbus ETH Dives” section listed below.
If the configuration process between Elara and the rectifier is not required, proceed to step X.
...
Make sure the Elara connected to the HUB and to the Power Center
אין רקטיפייר:
אין רקטיפייר אז פשוט רושמים את הIP הדיפולטי של הDFUN בPOWER CNETER הRANGE ולא אותו מספר
NETWORK too
צריבה ושמירה
לבדוק אלרה IP
...
לרשום IP נכון
...
add Modbus eth driver
...
Change IP
...
Open the PowerCenter (if the power center was already open, close it, and re-open it).
...
Open the “Active Device” drop-down menu and select “Elara”.
...
Open the “Connect Via” drop-down menu and select the relevant Serial COM port.
...
4. Navigate to the “Elara” tab.
...
5. Navigate to the “Configuration” tab
6. Click the “Read Configuration” button.
...
7. In the Configure tab click “Add Port 1 Device”.
...
8. The “Elara – Modbus Device Configuration” window will pop up:
a. Open the “Devices” first drop-down menu and select “AC_ Meter”.
b. Open the “Devices” second drop-down menu and select “CE42.”
c. Choose the most suitable ring according to the size conversion ratio.
...
d. Input the ID of the sensor in the “Physical Device ID” & “Virtual Device ID” (according to the previous configuration).
...
e. Make sure the “Device Budrate” is 19200, as you set it earlier.
f. Click “Apply”.
9. Click the “Write Configuration” button to save the changes.
...
10. Click the “Reset” button.
...
11. Navigate to the “Status” tab to view the status of the AC Meter.
...
necessary, change the IP address manually before proceeding to the “Adding Modbus ETH Dives”.
Double-click the “Network” row
...
2. Change the data settings to the following values:
Network Mask - 255.255.255.0
Network Gateway - 192.168.8.1
Elara IP - 192.168.8.101
...
3. Click on “Write Configuration”