The availability time is calculated by accumulating the time between records where the relevant asset was connected. The time will be accumulated only if the time difference between the subsequent records is less than 15* minutes. In addition, if the calculated availability value is larger than the Data Availability value, the value will be assigned with the Data Availability value.
Field Name | Field Description | Why this field is interesting / how it is calculated |
---|---|---|
Fuel X | Total hours the fuel sensor was connected | Based on records where Site_Global.Fuel_X_Discconected = No |
Generator X | Total hours the generator panel was connected | Based on records where Generator_X.Disconnected = No |
Unit Offline | Total hours data was not collected | 24 hours - Data Availability hours |
| Total hours the lithium-ion batteries were connected on average (sum of all batteries availability time divided by the number of batteries) | The availability for each battery is calculated based on records where Smart_Battery_X_Disconnected = No |
| Total hours the extension devices were connected on average (sum of all extensions availability time divided by the number of extensions) | The availability for each extension is calculated based on records where Site_Global.EX20_X_Discconected = No |
Ex20 ETH Availability Avg. | Total hours the ETH extension was connected in average | |
Data Availability | Total hours data was collected. Data availability can be larger than online availability if the unit was offline but still collected information, and sent the information when the connection was back | Based on the time between subsequent records, with the time difference limit mentioned in "General" |
Online Availability | Total hours the site was online and passed data to the server | Based on records where Log = No |
Tenant X | Total hours the tenant’s meter was connected | Based on records where Colo_Meter_X.Disconnected = No |
Rectifier X | Total hours the rectifier’s panel was connected | Based on records where Rectifier_X.Disconnected = No |
*For Kentrox units, the time between subsequent records will be accumulated only if the time difference is less than 30 minutes.