Skip to end of banner
Go to start of banner

Rectifiers Fields

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 18 Current »

Field Name

Field Description

Calculation Method

Rectifier X Load Energy Initial [KWH]

The first record of the kWh value that was read from the rectifier, for the selected time range. 

Rectifier X Load Energy Final [KWH]

The last record of the kWh value that was read from the rectifier, for the selected time range.

Rectifier X Load Energy Total [KWH]

The total energy (kWh) that was converted by the rectifier, for the selected time range.

Rectifier X Solar Initial [KWH]

The first record of the solar kWh value was read from the rectifier, for the selected time range.

Rectifier X Solar Final [KWH]

The last record of the solar kWh value was read from the rectifier, for the selected time range.






Rectifier X Solar Total [KWH]


The total solar production (kWh) for the selected time range, as read from the rectifier.

The kWh difference between 2 subsequent records will be aggregated if the following are true:

  1. The difference is positive. 

  2. Compare the current record to the last valid record

  • If the time difference > 60min > the extrapolation of the value for the total kWh of the day is less than 300 kWh.

  • Otherwise, the extrapolation of the value for the total kWh of the day is less than 10,000 kWh.

Rectifier X - V Min/Max/Avg* [V]

The maximum, minimum, and average DC voltage of the site, as read from the rectifier.

Rectifier X - Battery I Min/Max/Avg* [A]

The maximum, minimum, and average current of the battery, as read from the rectifier.


Rectifier X - I Input avg* [A]


The average of the rectifier's battery current measurement and load current measurement.

The average of Rectifier_X.I_Load + Rectifier_X.I_Battery. The value is aggregated if it is larger than 5A and smaller than 250A.

Rectifier X - Battery charging I avg* [A]

The average current that was used to charge the batteries, as read from the rectifier.

Rectifier X - Min/Max/Avg* Load Current [A]

The maximum, minimum, and average current of the rectifier's load output.

Rectifier X - Min/Max/Avg* Internal Temp [Celsius]

The maximum, minimum, and average internal temp of the rectifier.

Rectifier X - Min/Max/Avg* Batt. Temp [Celsius]

The maximum, minimum, and average internal temp of the battery.

This field based on the analog detailed field "Rectifier_X.Temperature_Battery [Celsius]".

Rectifier X - Max Solar Cell Power [W]

The maximum solar power that was supplied in the selected time range was read from the rectifier.

SOLAR_Module X V Max/Avg* [V]

The maximum and average voltage of the solar module for the selected time range.

Based on the detailed fields Rectifier_Y.Solar_Voltage_X [V]

X=1->4, Y=1->5

SOLAR_Module X I Max/Avg* [A]

The maximum and average current of the solar module for the selected time range.

Based on the detailed fields Rectifier_X.Solar_Current_X [V]

X=1->4, Y=1->5

Rectifier X - Communicating Solar Modules Max

Maximum number of modules that communicate with the rectifier.

Rectifier X - Communicating Rectifier Modules Max

*Zeros are ignored in the calculation of averaged fields