Field Name | Field Meaning and Logic |
---|---|
Grid Power | Energy assets such as grids, generators, and batteries can be monitored through multiple data sources - meters, control panels, etc. A global field considers all data sources and prioritizes them. Those fields will be used in the system for the displays, source logic, and summary fields (and as a result - in the system dashboards). |
DG 1/2 Load Power | |
Battery Power | |
Consumers Load Power | This field sums up all the power which is being consumed on site. The result value is the maximal value between the tenants' power to the rectifiers' power, added to the power of all the air conditioners on site. |
Sources Load Power | This field sums up all the power produced by energy assets on-site - grid, generators, and solar. |
Entrance_Configured | Indicates whether the alarm has been configured or not False - Not configured True - Configured |
Entrance_Alarm | Indicates if the site entrance gate/door is open False - Entrance open True - Entrance close |
Alarm_Consumers_Load_Drop | If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active These alerts are activated when the site/tenant's consumption falls below 50% of the average for the previous seven days (the average is updated every night according to the summary report). Where the tenants have relocated or used more than one meter per tenant, the average is calculated according to the tenant, not the power meter, so:
|
Alarm_System_Integrity | This digital alarm, will be activated if one of the components on the site (which is not an Elara gateway) is disconnected. |
Solar Power | According to the following priority, we will take the result for the power field if the result is larger than 0:
|
General
Content
Integrations