The Inverter\Charge Controller\AC Voltage Stabilizer card illustrates how the inverter\charge controller is used on the site. The card will appear on the screen only if the inverter\charge controller\AC Voltage Stabilizer is configured.
The display of the title will be defined as follows:
“Charge Controller X" If Inverter_X.Is_Inverter_AC1 and Inverter_X.Is_Inverter_AC2 are both false
"Ac Voltage Stabilizer X" if “Is_Inverter_PV”, “Is_Inverter_Battery”, “Is_Inverter_Wind” are all false
"Inverter X" otherwise
Main View
The Subtitle is the inverter model - (Inverter_X.Device_Type).
The data in the main card will change according to the inverter type:
Battery & Solar: Is_Inverter_Battery is true and Is_Inverter_PV is true:
Solar Power - the sum of Inverter_X.Solar_Current_1..4 * Inverter_X.Solar_Voltage_1..4
Battery Power - Inverter_X.Battery_Current * Inverter_X.Battery_Voltage
Battery SOC - Inverter_X.Battery_SOC
Only Battery: Is_Inverter_Battery is true and Is_Inverter_PV is false:
Battery Power - Inverter_X.Battery_Current * Inverter_X.Battery_Voltage
Battery SOC - Inverter_X.Battery_SOC
Battery Temp - Inverter_X.Battery_Temperature
Only Solar: If Is_Inverter_PV is true and Is_Inverter_Battery is false:
Solar Current - the sum of Inverter_X.Solar_Current_1..4
Solar Voltage - an average of Inverter_X.Solar_Voltage_1..4
Solar Temp - max of Inverter_X.Solar_Temperature_1..4
Wind: If Is_Inverter_wind = True:
Wind Power- the sum of Inverter_X.Wind_Power_2 + Inverter_X.Wind_Power_1
Expanded View
Status - Inverter_1.Status - Only displays if the value is greater than 0. The relevant text will be displayed in accordance with the status value.
Wind - Power 1, Power 2
Battery - Indicates whether Is_Inverter_Battery is true.
Battery Voltage
Battery Current
Battery Temperature
Battery SOC (precision 0)
Battery SOH (precision 0)
Solar - For each solar module 1..4, a separate card will be displayed. Each card's module includes:
Title - Solar Y
Voltage - Inverter_X.Solar_Voltage_Y
Current - Inverter_X.Solar_Current_Y
Temperature- Inverter_X.Solar_Temperature_Y
Total kWh - Inverter_X.Solar_KWH_Y
AC X - Indicates if Is_Inverter_AC1 is true.
Voltage Phase 1,2,3 - Inverter_X.AC_Voltage_Phase_1..3 (V)
Current Phase 1,2,3 - Inverter_X.AC_Current_Phase_1..3 (A)
Frequency - Inverter_X.AC_Frequency (Hz)
PF - Inverter_X.AC_Power_Factor
Total kWh - Inverter_X.AC_Total_KWH
Alarms - Solar_1..4_Alarm_Active - show if true
Control button - clicking the control will open a drop-down with the options:
Inverter Start, Inverter Stop - Use the inverter control panel to start and stop the generator
Inverter Reset
After clicking one of the options, a confirmation message will appear as a popup. "Are you sure? The selected command will be applied to the inverter".