Introduction

 The EX-20 extension enables the expansion of connectivity options that operators require in their sites.

It also converts RS232 to RS485, making it possible for Elara to communicate with different devices that have different communication protocols.

Catalog information

Technical Specification

Power Supply

9 – 30V

Power Consumption

0.12W average (approx.) @12V approx. 10mA

Weight

80g (approx.)

Storage temperature

-40 – 85 Celsius

Working temperature

-20 – 70 Celsius

Serial communication

RS485/RS232/ CAN (Model specific)

Max. relative humidity

90%

0 – 5V analog input

4

0 – 15V analog input

8

Digital inputs (Negative)

5

Open collection output

1

Preparation

Before getting started, make sure you have the following items:

Tools:

  • Screwdriver flat & Philips

  • Electrical wires

  • Wire stripping tool

  • RS-485 to USB adaptor (for connecting to the Elara via PowerCenter - make sure to install the drivers)

  • Voltmeter (for troubleshooting voltage issues)

Hardware:

  • EX20 Galooli device

  • Laptop/ PC

  • PowerCenter application installed - with credentials

  • Zon Max application installed – with credentials

  • Elara tray/shelter - including the Terminal blocks

Wiring and installation

Before getting started with the installation, make sure you have the wiring diagram relevant to your project.

Mounting the sensor

  1. Locate the designated space for the EX20 on the upper DIN rail of the Elara’s ShelterBox/ Tray.

  1. Verify that the EX20 unit is connected to all of its relevant interfaces:

Interfaces

Wires

 

 

Terminal Blocks IOs

·         Analog 1 à 12

·         1 Output

·         Digital 1,2,3,4 & 7

·         RS-232   TX RX

 

Terminal Blocks Power

·         -IN (GND)

·         +IN (+12V DC)

 

Elara’s 2nd RS-485 terminal

·         RS485A

·         RS485B

 

Configuration The ID of the EX20 in Power Center

  1. Connect the EX20 to a 12V DC power supply.

  2. Connect the EX20 to the computer via the RS 485 to USB converter.

 

  1. Open the PowerCetner app.

  2. Open the “Active Device” dropdown menu and Select “Power Device.”

  1. Open the “

Connected via” dropdown and Select the relevant “Com port.”

  1. Navigate to the “

EX20” tab on the top toolbar.

  1. Click on “

Set Device ID”, a pop up window will appear, set the ID of the Ex20 device according to your Wiring Diagram and apply.

  1. Click the “

Write All Parameters” button.

  1. Disconnect the EX20 from the current setup.

Configuration of the Elara in Power Center

  1. Connect the EX20 to a 12V DC power supply – from Termnial Blocks.

  2. Connect the EX20 to the second RS 485 Elara port.

  3. Using the RS485 to USB converter, connect the PC to the DLS & BZR ports on the Terminal Blocks.

  1. Open the PowerCetner app.

  1. Open the “

Active Device” dropdown and Select “Elara.”

  1. Open the “

Connected via” dropdown and Select the relevant “Com port.”

  1. Navigate to the “

Elara” tab.

  1. Navigate to the “

Configuration” tab.

  1. Click the “

Read Configuration” button.

10. Click the “Add Port-2 Device” botton, and the” ELARA-Modbus Device Configuration” window will pop up.

11. In the “Elara – Modbus Device Configuration” fill in the relevant fields:

a.     In the first “Device” dropdown list, select “Galooli”.

b.    In the second “Device” dropdown list, select “EX20”.

c.     In the “Physical & Virtual Device ID”, input the ID number that you have configured previously, according to your wiring diagram.

d.    In “Device Baudrate” select 19200.

e.    Click “Apply”.

12. Click the “Write Configuration” button.

13. Click the “Reset” button.

14. After the unit has reset, navigate to the “Status” tab, and verify that you can view that the EX20 is connected.

 