Linking Multiple Devices into a Single Virtual Device

Linking Multiple Devices into a Single Virtual Device

Overview

In scenarios where the total cable diameter does not allow measuring current with a single CT ring, the current must be split across multiple CT rings and meters. A new capability allows linking multiple meters into one virtual meter so the system treats them as a single logical device.

This configuration is handled at the device level, while the cloud aggregates and presents the values correctly.

Use Case

  • Multiple CT rings are required to measure total current.

  • Each CT ring is connected to a separate DC meter.

  • The meters must be represented as one meter in the system.

Configuration Steps

  1. Virtual ID Configuration

    • Configure all relevant meters with the same Virtual Device ID.
      Example:

      • Solar use case: Virtual ID = 34

      • Any other use case: use the required Virtual ID.

1.png
  1. Linked Device Setting

    • Select one of the meters and mark it as Linked Device in the Modbus Device Configuration.

    • All other meters remain unlinked but share the same Virtual ID.

2.png

Status & Data Representation

After configuration:

  • Connection Status:

    • The aggregated virtual meter will be displayed as Connected if at least one of the linked devices is in Connected status (OR logic).

  • Total Output KWH: Displayed value is the sum of total energy from all linked meters.

  • Voltage: Displayed value is the maximum voltage among all linked meters.

  • Current: Displayed value is the sum of currents from all linked meters.

The cloud automatically handles aggregation and presents correct values as if coming from a single physical meter.

image-20260406-072205.png

Notes & Limitations

  • You can link more than two meters — link as many as required.

  • This mechanism is not limited to CE DC Multi-Channel meters.

  • Any supported meter type can be linked using this method.