USR-IO (Device Extension - Supported Product)

USR-IO (Device Extension - Supported Product)

The USR-IO series is a flexible industrial I/O solution that functions as both a data logger and an extension module, offering reliable data acquisition and remote control capabilities via Modbus RTU over RS485, with configurable analog and digital I/O combinations to suit diverse integration scenarios.

image-20250507-084403.png

Supported Model

  • USR_io0080-8do

  • USR_io0404_4ao_4ai_voltage

  • USR_io0440_4do_4ai_current

  • USR_io4040_4do_4di

  • USR_io8000_8di

Features

  • Flexible I/O Configuration

  • Modbus RTU Protocol Support

  • Data Logger Functionality

  • Analog Input & Output Support

  • Extension Module Capability

  • Status Indicators

  • Industrial Design

  • Robust Electrical Protection

  • Factory Reset Function

  • 12–24V DC Power Supply

Hardware Specifications (USR-IO0404)

Items

Description

Items

Description

Interface

RS485

Default: 9600, NONE, 8, 1

Options for band rate: 4800, 9600, 115200, 230400

Parity bit: NONE, EVEN, ODD

Data bits: 8

Stop bit(s): 1, 2

Physical Specification

Dimensions

79.6*58*110(mm)

Installation

DIN rail mounting & Panel mounting

Status LEDs

 

POW

Steady on: Power supply is normal

Off: No power supply or abnormal power supply

WORK

Power is on, and the device is ready. System is booted up and running

DO

Steady on: The channel output is activated

DI

Steady on: The channel is activated input signal

Power

Power 2-pin socket

DC: 12-24V

Protection

EMC Protection

Level 3, IEC 61000

Watchdog

Hardware & Software watchdog

Flame retardant rating

V0, burning stops within 10 seconds on a vertical part allowing for drops of plastic that are not inflames.

Temperature

Operation temperature

-25℃ ~ +75℃

Storage temperature

-40℃ ~ +105℃

Humidity

Operation Humidity

5%~95% (non-condensing)

I/O

DI

Digital opto-isolated input (0 -2 V detected as logic low,9 -36 V detected as logic high)

Not supported in USR-IO0404 Model

AI

Analog input 4-20mA

DO

Relays, the endurance is 100,000 operations. DC contacts rating @R (at resistive load) 3A / 30V DC. AC contacts rating @R (at resistive load) 3A / 250V AC, NO

Not supported in USR-IO0404 Model

AO

Analog output: voltage output: 0-10V, current output: 4-20mA

Modbus

Slave address

Range: 1~255 Default: 1

Pinout (USR-IO0404)

AO-Analog Output

AI-Analog Input

image-20250507-090044.png

Wiring

Fan Wiring

sd.jpg

Power Center Configuration

ID Configuration

  1. Connect the RS485 converter to the PC/laptop and connect the other ends of the wires to the Data Logger.

  2. Open Power Center > Open the “Active Device” drop-down menu, and select the “Power Device”

  3. Click on “Services Center” > “DataLogger USR-IOxx” > Set the “Communication Baudrate” to 9600 > Check the “ID Scan Mode” – to find the current ID default of the device.

Please note! If the current device ID is set according to your wiring diagram, then no additional action is needed, and move on to the next stage.

  1. Click “Next

  2. In “Device ID” – set the ID device according to your wiring diagram, then click the “Set New Configuration” button.

Please note! Make sure that the “Communication Baudrate” stays on 9600.

10. Click “Yes” when a window will pop up.

12. Once the Power Center detects the device, values will appear in the “Reading Results” section.

Device Configuration

image-20250525-063753.png

Manufacturer Data