Tray Set

Tray Set

The Galooli Tray Set is a durable indoor mounting solution designed to host a DC-DC converter, a Galooli gateway, and expansion modules. It features terminal block connections for simplified wiring and faster installation.

The tray structure varies depending on the gateway model.

The Tray Set is compatible with standard cabinets and is designed for installation in a 19-inch rack with a 2U height.

Elara Gateway Tray Set

Ultragate Gateway Tray Set

image-20251203-074410.png

Supported Models

Item Name

Galooli PN

Gateway

Including/Remarks

Item Name

Galooli PN

Gateway

Including/Remarks

Tray for Ultragate 19'' 2U

 

400-UltraTry2U-5071

 

 

 

 

Ultragate

400-DcdCUI12V-028- Meanwell

Ready for battery installation

Tray Set for Ultragate 19'' 2U, Incl. DC-DC, SPD

 

400-UltraTry2U-5071-SET

400-UltraTry2U-5071

400-DcdCUI12V-028- Meanwell

400-EXSPD-507 EX-SPD

Ready for battery installation

Tray Set for Ultragate 19'' 2U, Incl. DC-DC, SPD, Backup Battery

 

400-UltraTry2UBattery -5071-SET

400-UltraTry2UBattery -5071

400-DcdCUI12V-028- Meanwell

400-EXSPD-507 EX-SPD

Battery

Cables

Tray for Elara 19'' 2U

400-ElaraTry2U-5071

Elara

 

Tray Set for Elara 19'' 2U, Incl. DC-DC

400-ElaraTry2USET-507

 

Elara Tray to Ultragate Tray Replacement Kit

400-ElaratoUltraTry2U-5071

Elara To Ultragate

If an EX20 is present in the tray, the connection method changes after replacing the KIT.
Once the KIT is replaced, connect the power and communication cables directly from the terminal block to the EX20. To identify the correct inputs, refer to the stickers added to the KIT that indicate the connection details.

After that, connect all sensors directly to the EX20 instead of the terminal block.

Clients are required to order SPD units separately, based on the number of trays needed.

Tray Set for Axiomtek

(Not Supported)

400-AXITry2U-5071

Axiomtek

Not Supported

Tray Set for TechBase 19"" 2U, Incl. DC-DC

(Not Supported)

 

400-TehTry2U-5071

Techbase

Not Supported

Technical Specification

Size

Elara – Length: 40 cm × Width: 41 cm × Height: 8 cm
Ultragate – Length: 45 cm × Width: 41 cm × Height: 8 cm

Weight

Elara - 7 kg
Ultragate - 8 kg

 

Standards and Certification

  • ISO 9001

  • ISO 14001

  • ISO 45001

  • IEC 62368-1:2018

  • EN 62208:2011

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tray Set Parts

image-20241009-091720.png
Blank Panel
image-20241009-091746.png
2 Side Rails
Elara Tray Set
image-20251203-074434.png
Ultragate Gateway Tray Set

 

Data Sheets

Cabinet Layouts

Ultragate Tray Set Layout

In telecom sites we have many sensors and panels, therefore, we created this efficient tray, to help manage all the wires, and to be on top of things.

  • The specification applies to both the Tray Set and the Metal Enclosure Set.

  • There is dedicated compatibility between the Ultragate gateway and the Tray Set/Metal Enclosure Set.

image-20251203-082148.png

Main Input Fuse

This is the main fuse and input of electricity for the tray, it can receive from +18VDC to +75VDC, the main fuse need to be connected to the DC to DC power converter.

DC to DC Converter

The converter converts the input voltage (18VDC-75VDC) to +12V, since most of the sensors and devices, including the gateways, are working on +12VDC.

Grounding

Grounding is made to protect the sensitive electrical equipment in the tray, the grounding resistance should not be more than 5Ω.

GND & +12V Terminal

Extension terminal for GND and +12V power.
These are the main power slots for all the consumers in the tray, it is receiving power from the DC to DC converter. Any device in the tray should consume power only from the terminal blocks.

RS485 Terminal

Extension terminal for the gateway RS485 port, to provide a serial connection between the gateway and the other devices and sensors on the site.
The orange terminal is for Port A and the blue wires are for Port B

Gateway Slot

The gateway slot is a place for the gateway on the din rail, with the exact length of the green connectors, dedicated for the gateway.

Gateway Terminal

All the inputs & outputs of the gateway & EX20 are extended to the gray terminal, to have organized & comfortable connections to the devices.
Each input in the gray terminal directly extends the actual input in the gateway or EX20.

Hatch Sensor

The Hatch Sensor exists to indicate if the tray is opened.
As a convention, it always will be connected to the 5th input of the gateway.

Data Logger Slot

The Data Logger extension enables the expansion of the gateway

With the Data Logger connected to the gateway, a greater quantity of analog and digital sensors may be connected to the gateway.

Surge Protection Device (SPD) Slot

SPD is a device designed to protect electrical systems and equipment from voltage surges caused by lightning strikes, power grid fluctuations, or switching operations. It works by diverting excess voltage away from sensitive components. When connected to the Galooli Tray/Metal Box, a 13.5V charging voltage is required.

Backup Battery

For the adjusted Ultragate battery tray – an external 12V lead-acid battery is connected via a battery charger with a built-in SPD (Surge Protection Device) as an integral component of the tray/metal box.

For the battery to charge, the DC/DC must be set to 13.5V.
This should be an integral part of the process, including verification with a voltmeter to ensure the correct voltage is set.

image-20250330-051419.png
Battery Installation Video

An example of a fully installed tray with the Ultragate gateway (without the battery):

image-20251203-083411.png

Elara Tray Set Layout

In telecom sites we have many sensors and panels, therefore, we created this efficient tray, to help manage all the wires, and to be on top of things.

image-20241210-113136.png

Main Input Fuse

This is the main fuse and input of electricity for the tray, it can receive from +18VDC to +75VDC, the main fuse need to be connected to the DC to DC power converter.

DC to DC converter

The converter converts the input voltage (18VDC-75VDC) to +12V, since most of the sensors and devices, including the gateways, are working on +12VDC.

Grounding

Grounding is made to protect the sensitive electrical equipment in the tray, the grounding resistance should not be more than 5Ω.

Wiring Ducts

Wiring ducts are made for cable organization, all the cables from the sensors & devices on the site are designed to go through these wiring ducts.

GND & +12V Terminal

Extension terminal for GND and +12V power.
These are the main power slots for all the consumers in the tray, it is receiving power from the DC to DC converter.
Any device in the tray should consume power only from the terminal blocks.

RS485 Terminal

Extension terminal for the gateway RS485 port, to provide a serial connection between the gateway and the other devices and sensors on the site.
The orange terminal is for Port A and the blue wires are for Port B

Gateway Slot

The gateway slot is a place for the gateway on the din rail, with the exact length of the green connectors, dedicated for the gateway.

EX20-1/2 Slot

The EX20-1/2 (Extension Devices) slot is a place for the EX20 on the din rail, with the exact length of the green connectors, dedicated for the EX20.

Gateway & EX20-1/2 Terminal

All the inputs & outputs of the gateway & EX20 are extended to the gray terminal, to have organized & comfortable connections to the devices.
Each input in the gray terminal directly extends the actual input in the gateway or EX20.

Hatch Sensor

The Hatch Sensor exists to indicate if the tray is opened.
As a convention, it always will be connected to the 5th input of the gateway.

An example of a fully installed tray with the Elara gateway: