CE Transducer CE11 - Galooli Solution Configuration
Galooli Solution Layout Configuration
Log in to Galooli solution using your credentials.
Select the relevant unit you wish to configure.
Navigate to “Configuration” tab and click the “Device Configuration”.
Select or write the correct layout
5. Click on the “Section: Global DC Control”. Fill in the relevant data.
6. Save the data
Galooli Solution IO Configuration
Double click the relevant unit and navigate to “Configuration” tab >> “Device Configuration” >> “IO’s”.
a. Between Rectifier and Batteries (ID 40-44 on the wiring diagram):
Input Name | Input Type | Description |
Rectifier_X.I_battery | Analog | Current indication |
Rectifier_X.DC_Meter_Battery_disconnected | Digital | If communication exists or not |
b. Between Rectifier and Tenants (ID 50 -54 on the wiring diagram):
Input Name | Input Type | Description |
Rectifier_X.I_Load | Analog | Current indication |
Rectifier_X.DC_Meter_Load_disconnected | Digital | If communications exists or not |
c. As individual tenants (ID 60 –69 or 90 – 99 on the wiring diagram):
Collo_Meter_X_total_KWH | Analog | Power coming from all 3X phases |
Collo_Meter_X_V_L1 | Analog | Voltage value for phase - X |
Collo_Meter_X_I_L1 | Analog | Current for phase X |
Colo_Meter_X_ Disconnected | Digital | If communications exists or not |