5. Techbase NPE X500 M3 - Gateway Configuration

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 18 Next »

  1. The ethernet cable should be connected to the left socket (LAN1 - eth0) of the Techbase NPE X500 M3 and to the computer at the other end.

2. On your computer, set a static IP address of 192.168.1.10.

3. Enter the following IP address in the URL line of your browser - 192.168.1.11.

4. Please enter the following username and password:

User name - galooli

Password - galooli

5. When you have successfully entered the site, please click on the "Registration" button.

It is the same personal username and password that you use to access your Galooli platform (Web Solution & ZonMax).

6. As soon as you have entered your credentials successfully, please click on "System", then "Application Reset", and ensure that the status of your registration is "Valid".

Status

Meaning

Valid

Registration was completed successfully

Missing

The status before the registration

Failed

Registration failed. Please try again to register

7. Please click on "Configuration" and upload the configuration file you created in the previous step (gib file) to the “Parameters file” row.

8. In order to obtain an indication of the progress of the upload, go to "System" and ensure that all the parameters are correct and valid

Afterward, go to "Status" and ensure that the host is "True" and you will see all digital and analog devices connected to the Techbase NPE X500 M3. Verify that the sensors on the list are the same sensors you configured in the Power Center.

If the information is not displayed, you should upload the file again and then click "Application Reset".

9. As soon as you have successfully completed all the steps, you can move on to the next step - Techbase NPE X500 M3 Unit Creation.