Skip to end of banner
Go to start of banner

Energy Devices Fields

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 30 Next »

Field Name

Field Description

Calculation Method

Grid - PhX V Min/Max/Avg* [V]

The minimum, maximum, and average voltage of the grid phase for the selected time range.

Grid - PhX A Min/Max/Avg* [A]

The minimum, maximum and average current of the grid phase for the selected time range

Grid - kWH Initial/Final [KWH]

The first/last record of the kWh value that was read from the grid AC meter, for the selected time range.

Based on the detailed field AC_Meter_Grid.Total_KWH [KWH]




Grid - kWH Total [KWH]




The total kWh production of the asset for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

Grid - PhX Power Factor Max/Min [A]

The minimum, maximum and average power factor of the ATS phase for the selected time range.

ATS - PhX V Min/Max/Avg* [V]

The minimum, maximum, and average voltage of the ATS phase for the selected time range.

ATS - PhX A Min/Max/Avg* [A]

The minimum, maximum and average current of the ATS phase for the selected time range

ATS - kWH Initial/Final [KWH]

The first/last record of the kWh value that was read from the ATS AC meter, for the selected time range.

Based on the detailed field AC_Meter_ATS.Total_KWH [KWH]




ATS - kWH Total [KWH]




The total kWh that was read from the ATS meter for the selected time range.

Based on the detailed field AC_Meter_ATS.Total_KWH [KWH].

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

ATS - PhX Power Factor Max/Min [A]

The minimum, maximum and average power factor of the ATS phase for the selected time range.

ATS – DG KWH Total [KWH]

Summary calculation of the ATS total kwh when DG1\DG2 was on load

ATS – Grid KWH Total [KWH]

Summary calculation of the ATS total kwh when the Grid was on load

The difference between: (ATS KWH Total) - (ATS - DG kWh Total)

DGX - PhX V Min/Max/Avg* [V]

The minimum, maximum, and average voltage of the generator phase for the selected time range.

DGX - PhX A Min/Max/Avg* [A]

The minimum, maximum and average current of the generator phase for the selected time range

DGX - kWh Initial/Final [KWH]

The first/last record of the kWh value that was read from the generator AC meter or generator panel, for the selected time range.

Based on the detailed field AC_Meter_Generator_X.Total or Generator_1 power data



DGX - kWh Total [KWH]



The total kWh production of the generator that was read from the generator AC meter or generator panel for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

DGX - PhX Power Factor Min/Max [A]

The minimum, maximum and average power factor of the phase for the selected time range.

DGX - Coolant Temp Min/Max [Celsius]

The minimum and the maximum coolant temperature of the geenrator X.


DGX - Min, Max, Avg* Load [KW]

The minimum, maximum and average load of the geenrator for the selected time range. Generator load (kW) is used to measure the real electric power provided by the generator.
Monitoring the generator load is necessary for assuring the generator is operating under the proper conditions, reducing maintenance costs and frequent replacements.

If AC_Meter.Generator_X is configured - the calculation is the sum of all phases (Y=1,2,3): (AC_Meter_Generator_1.V_LY * AC_Meter_Generator_1.I_LY * AC_Meter_Generator_1.PF_LY) divided by 1000.

Else, the calculation is the sum of all phases (Y=1,2,3):

(Generator_1.Gen_VY * Generator_1.Gen_IY), multiplied by Generator_1.Power_Factor and divided by 1000. If the power factor is 0, a default value of 0.95 is used.

SOLAR - PhX V Min/Max/Avg* [V]

The minimum, maximum, and average voltage of the solar meter phase for the selected time range.

SOLAR - PhX A Min/Max/Avg* [A]

The minimum, maximum and average current of the solar meter phase for the selected time range

SOLAR - kWh Initial/Final [KWH]

The first/last record of the kWh value that was read from the solar meter, for the selected time range.

Based on the detailed field Meter_Solar.Total_KWH [KWH]




SOLAR - kWh Total [KWH]




The total kWh production of the solar for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

SOLAR_Module X V Max/Avg* [V]

The maximum and average voltage of the solar module for the selected time range.

Based on the detailed fields Rectifier_Y.Solar_Voltage_X [V]

X=1->4, Y=1->5

SOLAR_Module X I Max/Avg* [A]

The maximum and average current of the solar module for the selected time range.

Based on the detailed fields Rectifier_X.Solar_Current_X [V]

X=1->4, Y=1->5

WIND - PhX V Min/Max/Avg* [V]

The minimum, maximum, and average voltage of the wind meter per phase, for the selected time range

WIND - PhX A Min/Max/Avg* [A]

The minimum, maximum and average current of the wind meter per phase, for the selected time range

WIND - kWh Initial/Final [KWH]

The first/last record of the kWh value that was read from the wind meter, for the selected time range.

Based on the detailed field Meter_Wind.Total_KWH [KWH]




WIND - kWh Total [KWH]




The total kWh production of the wind turbine for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

The availability time is calculated by accumulating the time between records where the relevant asset was connected. The time will be accumulated only if the time difference between the subsequent records is less than 15 minutes. In addition, if the calculated availability value is larger than the Data Availability value, the value will be assigned to the Data Availability value.

*Zeros are ignored in the calculation of averaged fields

  • No labels