Fuel Sensor Power Troubleshooting
How to Detect the Fault? | Fault Description | Troubleshooting Steps |
No Power | When the Fuel sensor is connected to the power source, it does not receive any power |
|
No Communication | When the Fuel sensor is connected to the communication Terminal block, it does not communicate with the Elara unit |
|
Power Center Communication Troubleshooting
Configuration for Holykell fuel sensor is done through the services tab at the top left section of Power center .
No communication | The fuel sensor is receiving power, but the unit is not connected to Elara or K2 | Connect your serial converter to the ports for RS 485 B and pin 4 for RS485 A |
Read all configurations communication protocol should be set at Device ID :15 Baudrate :19200 | ||
| Open the Holykell configuration Tab Set Baudrate at 19200 | Id Scan the fuel sensor and if it lands on a different ID from 15. Click on next Icon and set the default ID and Baudrate as 15 and 19200 respectively. If no communication is present |
| Open the Holykell configuration Tab Set Baudrate at 9600 | Id Scan the fuel sensor and if it lands on a different ID from 15. Click on next icon and set the default ID and Baudrate as 15 and 19200 respectively.
|
| The device is communicating but giving the wrong data | The Fuel sensor should be taken out of the fuel tank and held straight on a flat surface. Ensure the tip of the fuel sensor is 2cm from the base of the fuel’s sensor securing rod Read all configurations from the Holykell fuel sensor calibration tab on the Services center. Once done perform the Zero calibration on the fuel sensor.
|