The Door Sensor provides an open or close indication
Features:
1 3/8” to 3” operating gap
24” armored cable
Corrosion-resistant
Alnico 6 magnet
Anodized aluminum housing
Versatile installation can be mounted onto doors, gates, and generators
Strong magnetic field ensuring constant vigilance and security
Technical Specification | |
Contact rating: | 3VA |
Contact type: | N.O. / N.C. |
Max carry current: | 0.5 Amp |
Max switching current: | 0.5 Amp |
Breakdown voltage: | 200VDC Min. |
Operating gap: | 1 3/8” to 3” |
Mounting method: | Screws |
Operating temperature range: | 32°F to 120°F (0°C to 49°C) |
Sensor description & assembly
The sensor is made up of two metal rods. The first one includes the sensor processor, and the second one is a magnet, which provides an indicator if the door is opened or closed.
Wiring and installation
Before getting started with the installation, make sure you have the wiring diagram relevant to your project readily available.
Connect the Black & Green wires according to the following scheme:
Black wire – to a +12V DC power source.
Green wire – to the dedicated port on the Elara/EX device.
NC red wire – Do not use.
Connect the IO wire (Green) to the dedicated IO port on the Elara device or the Terminal block.