Supported Models
LgLG-chemChemCommunication Method
The network connection plug is RJ48 with the following pinout: RS485A- Pin 3, RS485B -Pin4, GND -Pin1 and Pin10RS485 connectionWiring Diagram
For this particular battery if there is no RMS cable connected it used 10pin RJ50 connectors on installations where we do not have the RJ50-DB9 cable for RMS. Below is the direct connection to the master battery.
Comm | RJ50 bottom side ports |
A | 4,5 |
GND | 1,10 |
B | 2,3 |
*count is from left
...
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
...
Part #
...
Function
...
1
...
Fan
...
2
...
Status indicators
...
3
...
RJ48 port for intra rack communication cable
...
4
...
RJ48 port for higher-level communication cable
...
5
...
Positive connector (+)
...
6
...
Power Terminal compartment
...
7
...
Negative connector (-)
...
8
...
On/Off button
...
9
...
Dry contact
...
10
...
Handle
...
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
...
View file | ||
---|---|---|
|
Network configuration
מה צריך לקנפג בסוללות עצמן
להבדיל מהאמירה הרגילה, פה הייתי רוצה שתשים מונה (או הערה) על הקינפוג של הPower center כי יש שם שני תרגילים שונים מאוד בין הסוללות, וכולם תמיד מתבלבלים באיזה תרגיל עושים לאיזו סוללה (לדוגמא, עכשיו צפריר הסתבך עם זה בפיליפינים. הוא ידע לפרט)
...
...
Network configuration
Device Baudrate | 19200 |
---|---|
Device ID | All modules share the same master device ID (usually 0x01). see Galooli configuration tool for module detailes |
Alarms List
Critical | Urgent | Non Urgent | Observation |
---|---|---|---|
"Cell Over Voltage Fault 2" | "Cell Over Voltage Fault 1" | "Cell Over Voltage Warning" | "Cell Over Voltage Alarm" |
"Cell Under Voltage Fault 2" | "Cell Under Voltage Fault 1" | "Cell Under Voltage Warning" | "Cell Under Voltage Alarm" |
"Over Charging Current Fault 2" | "Over Charging Current Fault 1" | "Over Charging Current Warning" | "Over Charging Current Alarm" |
"Over Discharging Current Fault 2" | "Over Discharging Current Fault 1" | "Over Discharging Current Warning" | "Over Discharging Current Alarm" |
"Available charge limit over Fault 2" | "Over Temperature Fault 1" | "Over Temperature Warning" | "Over Temperature Alarm" |
"Available discharge limit over Fault 2" | "Under Temperature Fault 1" | "Under Temperature Warning" | "Under Temperature Alarm" |
"Over Temperature Fault 2" | "Cell Voltage Difference Fault 1" | "Cell Voltage Difference Warning" | "Over SOC Alarm" |
"Under Temperature Fault 2" | "Module Temp Difference Fault 1" | "Available charge limit over Warning" | "Under SOC Alarm" |
"Internal Communication Fault 2" | "Available charge limit over Fault 1" | "Available discharge limit over Warning" | "Module Temp Difference Alarm" |
"Pack Under Voltage Fault2" | "Available discharge limit over Fault 1" | "Under SOC Warning" | "Available charge limit over Alarm" |
"BMS HW Fault 2" | "Internal Communication Fault 1" | "Over SOC Warning" | "Available discharge limit over Alarm" |
"External Communication Fault 1" | "Under SOH Alarm" |
Supported Parameters
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Battery_SOC_Percentage | Smart_Battery_X.SOC | |
Battery_SOH | Smart_Battery_X.SOH |
|
Voltage | Smart_Battery_X.Voltage [V] |
|
Current | Smart_Battery_X.Current [A] |
|
Cell_Voltage_Min | Smart_Battery_X.Cell_Voltage_Min [V] |
|
Cell_Voltage_Max | Smart_Battery_X.Cell_Voltage_Max [V] |
|
Temperature_1-2 |
Smart_Battery_X.Temperature_X[Celsius] | Temperature 1 - cell temperature Temperature 2 - cell temperature Since lithium batteries are prone to catching fire and exploding at high temperatures, there are two temperature meters for the same purpose. |
Battery_Cycles | Smart_Battery_X.Cycles |
|