Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

View file
nameEX20 Device.pdf

Image Removed

Introduction

 The EX-20 extension enables the expansion of connectivity options that operators require in their sites.

It also converts RS232 to RS485, making it possible for Elara to communicate with different devices that have different communication protocols.

Catalog information

...

Technical Specification

...

Power Supply

...

9 – 30V

...

Power Consumption

...

0.12W average (approx.) @12V approx. 10mA

...

Weight

...

80g (approx.)

...

Storage temperature

...

-40 – 85 Celsius

...

Working temperature

...

-20 – 70 Celsius

...

Serial communication

...

RS485/RS232/ CAN (Model specific)

...

Max. relative humidity

...

90%

...

0 – 5V analog input

...

4

...

0 – 15V analog input

...

8

...

Digital inputs (Negative)

...

5

...

Open collection output

...

1

Preparation

Before getting started, make sure you have the following items:

Tools:

  • Screwdriver flat & Philips

  • Electrical wires

  • Wire stripping tool

  • RS-485 to USB adaptor (for connecting to the Elara via PowerCenter - make sure to install the drivers)

  • Voltmeter (for troubleshooting voltage issues)

Hardware:

  • EX20 Galooli device

  • Laptop/ PC

  • PowerCenter application installed - with credentials

  • Zon Max application installed – with credentials

  • Elara tray/shelter - including the Terminal blocks

Wiring and installation

Before getting started with the installation, make sure you have the wiring diagram relevant to your project.

...

Mounting the sensor

  1. Locate the designated space for the EX20 on the upper DIN rail of the Elara’s ShelterBox/ Tray.

...

  1. Verify that the EX20 unit is connected to all of its relevant interfaces:

...

Interfaces

...

Wires

...

 

...

 

Terminal Blocks IOs

...

·         Analog 1 à 12

·         1 Output

·         Digital 1,2,3,4 & 7

·         RS-232   TX RX

...

 

...

Terminal Blocks Power

...

·         -IN (GND)

·         +IN (+12V DC)

...

 

...

Elara’s 2nd RS-485 terminal

...

·         RS485A

·         RS485B

...

 

Configuration The ID of the EX20 in Power Center

  1. Connect the EX20 to a 12V DC power supply.

  2. Connect the EX20 to the computer via the RS 485 to USB converter.

...

 

  1. Open the PowerCetner app.

  2. Open the “Active Device” dropdown menu and Select “Power Device.”

...

  1. Open the “

Connected via” dropdown and Select the relevant “Com port.”

...

  1. Navigate to the “

EX20” tab on the top toolbar.

...

  1. Click on “

Set Device ID”, a pop up window will appear, set the ID of the Ex20 device according to your Wiring Diagram and apply.

...

  1. Click the “

Write All Parameters” button.

...

  1. Disconnect the EX20 from the current setup.

Configuration of the Elara in Power Center

  1. Connect the EX20 to a 12V DC power supply – from Termnial Blocks.

  2. Connect the EX20 to the second RS 485 Elara port.

  3. Using the RS485 to USB converter, connect the PC to the DLS & BZR ports on the Terminal Blocks.

...

  1. Open the PowerCetner app.

  1. Open the “

Active Device” dropdown and Select “Elara.”

...

  1. Open the “

Connected via” dropdown and Select the relevant “Com port.”

...

  1. Navigate to the “

Elara” tab.

...

  1. Navigate to the “

Configuration” tab.

...

  1. Click the “

Read Configuration” button.

...

10. Click the “Add Port-2 Device” botton, and the” ELARA-Modbus Device Configuration” window will pop up.

...

11. In the “Elara – Modbus Device Configuration” fill in the relevant fields:

a.     In the first “Device” dropdown list, select “Galooli”.

b.    In the second “Device” dropdown list, select “EX20”.

c.     In the “Physical & Virtual Device ID”, input the ID number that you have configured previously, according to your wiring diagram.

d.    In “Device Baudrate” select 19200.

e.    Click “Apply”.

...

12. Click the “Write Configuration” button.

...

13. Click the “Reset” button.

...

14. After the unit has reset, navigate to the “Status” tab, and verify that you can view that the EX20 is connected.

...

The Ex20 extension enables the expansion different gateways like the Elara, Techbase, and Axiomtek.

With the Ex20 connected to the gateway tray/metal box, a greater quantity of analog and digital sensors may be connected to the gateway.

Features

  • 4 analog input (0-5V)

  • 8 analog input (0-15V)

  • 5 Digital inputs (Negative)

  • 1 Open collection output

  • 1 RS232 Gateway (Modbus host)

Hardware Specifications

Power Supply

9 - 30 V

Power Consumption

Full power mode

0.12 W average (Aprox.)

@12v aprox. 10mA

General purpose inputs

12 Analog inputs (0-5v / 0-15v available – Model specific)

8 digital inputs (Model specific)

Outputs

Open collector output (Model specific)
SSR dry contacts (Model specific)


Serial Communication

RS485 (Main) / Modbus host

RS232 (Model specific)

CAN (Model specific)

RS485 (Secondary – Model specific)

Storage Temperature

-40 - 85 Celsius

Working Temperature

-20 - 70 Celsius

Max. Relative humidity

90%

Weight

80g (Aprox.)


Output specifications

Output Type

Open Collector

Max. Continuous working current

200 mA

Over Current protection

300 mA (Aprox.)

Maximum working voltage

40 V


General-purpose analog inputs specifications

Reading Voltage range

0-5V / 0-15V

Reading Resolution

2 mV / 5mV

Reading Accuracy (max error)

2%

Max input voltage

40V


Negative digital inputs specifications

Low level threshold (Active)

1 V

High Level threshold

1.4V


Mechanical Dimensions

Length

86mm

Width

70mm

Height

58mm

 Status LEDs

Active state

Blinking pattern description

Pattern

Host Connected

Green, Fast blink (for a period of 10 Sec after each message from host)

Image Added

 

Gateway mode: No host, but data received at the RS232 port

Red, Fast blink (for a period of 10 Sec after each message from host)

Image Added

 

Idle State (No communication)

Red, short blink and long pause.

Image Added

Idle State (No Communication), Error condition

Red, (X>1) Short blinks and long pause.

Contact Galooli for detailed description on detection of fault state

 

Image Added

 

...

 Pinout

0-5V

0-5V

0-5V

0-5V

0-15V

0-15V

0-15V

0-15V

0-15V

0-15V

0-15V

0-15V

GND

PWRIN

RS485-A

RS485-B

DIG1

DIG2

DIG3

DIG4

RS232-TX

RS232-RX

DIG7

OUT

Pin#

Name

AN1

Analog 1

AN2

Analog 2

AN3

Analog 3

AN4

Analog 4

AN5

Analog 5

AN6

Analog 6

AN7

Analog 7

AN8

Analog 8

AN9

Analog 9

AN10

Analog 10

AN11

Analog 11

AN12

Analog 12

IN-

GND - Terminal Blocks Power

IN+

+12V DC - Terminal Blocks Power

RS485 A

RS485 A Communication pin

RS485 B

RS485 B Communication pin

DIG1

Digital 1

DIG2

Digital 2

DIG3

Digital 3

DIG4

Digital 4

RS232 TX

RS232 transmitted data

RS232 RX

RS232 received data

DIG7

Digital 7

OUT

Output

...