Supported Models
Vertiv M530B
Device IP | 192.168.1.2 |
Subnet mask | 255.255.255.0 |
Gateway | 192.168.1.1 |
Host IP (Web/Elara configuration) | 192.168.1.5 |
Vertiv M820D_ ACU_ PLUS
Vertiv M830D_ NCU
Device IP | 10.1.1.102 |
Subnet mask | 255.255.255.0 |
Gateway | 10.1.1.1 |
Host IP (Web/Elara configuration) | 10.1.1.103 |
Communication Method
ETHERNET/SNMPRead/Write Community
Vertiv M530B:
Read - public
Write - (keep it empty)Vertiv M820D_ ACU_ PLUS / Vertiv M830D_ NCU:
Read - public
Write - public
Device Configuration
To be announced
Supported Parameters (SNMP)
M530B
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Total_Output_KWH | Rectifier_X.Total Load Energy [KWH] |
|
Voltage | Rectifier_X.U_System [V] |
|
Current | Rectifier_X.I_Load |
|
Battery_Current | Rectifier_X.I_Rectifier |
|
Battery_SOC_Percentage | Rectifier_X.State_Of_Charge |
|
Internal_Temperature | Rectifier_X.Temperature_Internal [Celsius] | |
Battery_Temperature | Rectifier_X.Temperature_Battery [Celsius] |
|
Solar_W | Rectifier_X.Solar_Power [W] | |
Solar_KWH | Rectifier_X.Solar_Total_Power [KWH] |
|
Solar_Curent | Rectifier_X.Solar_Current [A] |
|
Comunication_Modules | Rectifier_X.Communication_Rectifier_Modules |
|
Comunication_Solar_Modules | Rectifier_X.Communication_Solar_Modules | |
Load_Used_Capacity | Rectifier_X.Used_Capacity |
M820D_ ACU_ PLUS
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Grid_Voltage_Phase_1-3 | TBA | |
Voltage | Rectifier_X.U_System [V] | |
Current | Rectifier_X.I_Load | |
Battery_Current | Rectifier_X.I_Rectifier | |
Battery_Temperature | Rectifier_X.Temperature_Battery [Celsius] | |
Temperature 2 | Rectifier_x.Module_Temperature_x [Celsius] | |
Battery_SOC_Percentage | Rectifier_X.State_Of_Charge | |
Load_Used_Capacity | Rectifier_X.Used_Capacity |
M830D_ NCU
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Total_Output_KWH | Rectifier_X.Total Load Energy [KWH] | |
Voltage | Rectifier_X.U_System [V] | |
Current | Rectifier_X.I_Load | |
Battery_Current | Rectifier_X.I_Rectifier | |
Battery_Temperature | Rectifier_X.Temperature_Battery [Celsius] | |
Battery_SOC_Percentage | Rectifier_X.State_Of_Charge | |
Solar_KWH | Rectifier_X.Solar_Total_Power [KWH] | |
Solar_W | Rectifier_X.Solar_Power [W] | |
Temperature 2 | Rectifier_x.Module_Temperature_x [Celsius] | |
Solar_1-8_Voltage | Rectifier_X.Solar_Voltage_X [V] | |
Solar_1-8_Current | Rectifier_X.Solar_Current_X [A] | |
Grid_Voltage_Phase_1-3 | TBA | |
Comunication_Modules | Rectifier_X.Communication_Rectifier_Modules | |
Comunication_Solar_Modules | Rectifier_X.Communication_Solar_Modules | |
Load_Used_Capacity | Rectifier_X.Used_Capacity |