Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Network Configuration

Device Baudrate

9600

  1. For configuring the physical ID when there are one or more batteries connected to one another, the following actions must be taken. As shown in the table, the "ADD" part must be configured according to the number of batteries, on each battery separately.

...

  1. Add a serial device in Power Center >> Choose "Smart Battery" >> "Changhong" >> Set the "Physical Device ID" and "Virtual Device ID" as follows and according to the number of batteries:

Number Of Batteries

Physical Device ID

Virtual Device ID

1

1

70

2

2

71

3

3

72

4

4

73

Supported Parameters

Power Center Parameters

System Parameters

Remarks

Current

Smart_Battery_X.Current [A]

Voltage

Smart_Battery_X.Voltage [V]

Battery_SOC_Percentage

Smart_Battery_X.SOC

Battery_SOH

Smart_Battery_X.SOH

Battery_Cycles

Smart_Battery_X.Cycles

Temperature_1

Smart_Battery_X.Temperature_X[Celsius]

Manufacturer Data

View file
nameChanghong Battery Data Sheet.pdf

View file
nameChanghong Battery Modbus.pdf