The Colocation/Tenant Card illustrates the data of the colocation meters and their usage on the site. If at least one colocation meter has been configured, the card will appear.

The card will display differently based on the type of tenants on the site; for example, a site with only AC or DC tenants will appear different from one with both AC and DC tenants

Tenants will be categorized and grouped based on AC Meters (installed/not installed per tenant) and will be presented in the same groups (AC Tenants/DC Tenants) in the Tenant/Colocation card.

Main View

  • Tenants names

  • Total Power - Sum of all tenant's power, power for each tenant: (Colo_Meter_X.V_L1 * Colo_Meter_X.V_I1 + Colo_Meter_X.V_L2 * Colo_Meter_X.V_I2 +Colo_Meter_X.V_L3 * Colo_Meter_X.V_I3)The AC/DC Power value comes from the fields "Site_Global.Tenants_Load_Power_AC [W]" and "Site_Global.Tenants_Load_Power_DC [W]" accordingly

  • Disconnected icon - appears if even one colo colocation meter is disconnected.

...

Expanded View

For each tenant separately:

  • Tenant name and the tenant meter number

  • Total kwh

  • Total DG kWh

  • Voltage - phases 1-3. Note that the number of lines is determined by the parameter Colo_Meter_X.AC_Meter. if true, 3 lines for voltage/current phases will be displayed, otherwise - only 1 line.

  • Current - phases 1-3. Note that the number of lines is determined by the parameter Colo_Meter_X.AC_Meter. if true, 3 lines for voltage/current phases will be displayed, otherwise - only 1 line.

...