Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Supported Models

Communication Methods

Read/Write Community

Eltek_SmartPack
eltek basic

RS485

Not Relevant


Eltek_SmartPack2
eltek basic
eltek ext



RS485/SNMP

Read - public
Write - v1private

Eltek_SmartPack2Touch
eltek basic
eltek ext



SNMP

Read - v1community
Write - v1private

Eltek_SmartPackS
eltek basic
eltek ext


SNMP

Network Configuration for ETHERNET/SNMP Connection

...

  1. Now that you have installed the appropriate gateway on site, it is time to connect it to the rectifier via the ethernet interface that is supported by the SmartPack 2 touch and SmartPack S.

  2. Connect the Galooli gateway to the rectifier using an Ethernet cable. The technical booklet will specify the specific name, model, and port of the gateway.

  3. In order to configure the Power Center and Galooli solution, please refer to the relevant links for your gateway:
    can be found by clicking here - https://galooli.atlassian.net/wiki/spaces/KP/pages/2882338951/Techbase+NPE+X500+M3+Installation+and+Configuration#Computer-Connections

...


4. Check the “Web-based configuration” to enable the web SNMP configuration.

...

  1. SNMP is now available

Supported Parameters (SNMP)

Power Center Parameters
SmartPack S
eltek basic
eltek ext

Power Center Parameters
SmartPack2 Touch
eltek basic
eltek ext

System Parameters

Remarks

(error)

Total_Output_KWH

Rectifier_X.Total Load Energy [KWH]

Voltage

Rectifier_X.U_System [V]

 

Current

Rectifier_X.I_Load

Battery_Current

Rectifier_X.I_Battery

Battery_SOC_Percentage

Rectifier_X.State_Of_Charge

Battery_Temperature

Rectifier_X.Temperature_Battery [Celsius]

Internal_Temperature

Rectifier_X.Temperature_Internal [Celsius]

Solar_Curent

Rectifier_X.Solar_Current [A]

Solar_KWH

Rectifier_X.Solar_Total_Power [KWH]

Solar_1-8_Voltage

Solar_1-4_Voltage

Rectifier_X.Solar_Voltage_X [V]


Solar modules data

Solar_1-8_Current

Solar_1-4_Current

Rectifier_X.Solar_Current_X [A]

DG_Signal

Rectifier_X.Generator Signal

Rectifier_Current

(error)

Rectifier_X.I_Rectifier [A]

Installed_Modules

(error)

TBA

Installed_Solar_Modules

(error)

TBA

 

Faulty_Modules

(error)

TBA

 

Faulty_Solar_Modules

(error)

TBA

 

Supported Parameters (RS485)

Power Center Parameters
SmartPack
eltek basic

System Parameters

Remarks

Serial-1

TBA

Total_Output_KWH

Rectifier_X.Total Load Energy [KWH]

 

Solar_KWH

Rectifier_X.Solar_Total_Power [KWH]

 

Rectifier_Current

Rectifier_X.I_Rectifier

Battery_Temperature

Rectifier_X.Temperature_Battery [Celsius]

Current

Rectifier_X.I_Load

Voltage

Rectifier_X.U_System [V]

Battery_SOC_Percentage

Rectifier_X.State_Of_Charge

Digital_Inputs

TBA

Digital_Outputs

TBA

Solar_Curent

Rectifier_X.Solar_Current [A]