Table of Contents | ||
---|---|---|
|
Supported Models | Communication Methods | Read/Write Community |
Eltek_SmartPack | RS485 | Not Relevant |
|
| Read - public |
Eltek_SmartPack2Touch |
| Read - v1community |
Eltek_SmartPackS |
|
Network
...
Configuration for ETHERNET/SNMP
...
Connection
Device IP | 192.168.10.20 |
---|---|
Subnet mask | 255.255.255.0 |
Gateway | 192.168.10.1 |
Host IP (Web/Elara configuration) | 192.168.10.21 |
Network
...
Configuration for RS485
...
Connection
Device Baudrate | 19200 |
---|
RS485 Wiring
...
Diagram
...
SmartPack
...
Configuration
Username - admin
Password - admin
...
SmartPack2
...
Configuration
...
Smart_Pack2 Touch
...
+ SmartPack S Installation & Configuration
Now that you have installed the appropriate gateway on site, it is time to connect it to the rectifier via the ethernet interface that is supported by the SmartPack 2 touch and SmartPack S.
Connect the Galooli gateway to the rectifier using an Ethernet cable. The technical booklet will specify the specific name, model, and port of the gateway.
In order to configure the Power Center and Galooli solution, please refer to the relevant links for your gateway.
Gateway | Link |
---|---|
Elara | |
TechBase |
SmartPack2 & S Touch SNMP Configuration
The following steps should be taken as soon as you receive your new “SmartPack 2 and S Touch Rectifier”:
1. In order to activate the SNMP option after installation, login to the rectifier controller and copy your
specific MAC address.
...
2. You will need to contact a representative from "Eltek" to activate the SNMP feature; you will need to
provide the MAC address from the previous paragraph and ask for a "license key.”
3. Once the "license key" has been reserved from "Eltek", enter it and proceed to the next step.
...
4. Check the “Web-based configuration” to enable the web SNMP configuration.
...
SNMP is now available
Supported Parameters (SNMP)
Power Center Parameters | Power Center Parameters | System Parameters | Remarks |
---|---|---|---|
Total_Output_KWH | Rectifier_X.Total Load Energy [KWH] | ||
Voltage | Rectifier_X.U_System [V] |
| |
Current | Rectifier_X.I_Load | ||
Battery_Current | Rectifier_X.I_Battery | ||
Battery_SOC_Percentage | Rectifier_X.State_Of_Charge | ||
Battery_Temperature | Rectifier_X.Temperature_Battery [Celsius] | ||
Internal_Temperature | Rectifier_X.Temperature_Internal [Celsius] | ||
Solar_Curent | Rectifier_X.Solar_Current [A] | ||
Solar_KWH | Rectifier_X.Solar_Total_Power [KWH] | ||
Solar_1-8_Voltage | Solar_1-4_Voltage | Rectifier_X.Solar_Voltage_X [V] |
|
Solar_1-8_Current | Solar_1-4_Current | Rectifier_X.Solar_Current_X [A] | |
DG_Signal | Rectifier_X.Generator Signal | ||
Rectifier_Current |
| Rectifier_X.I_Rectifier [A] | |
Installed_Modules |
| TBA | |
Installed_Solar_Modules |
| TBA |
|
Faulty_Modules |
| TBA |
|
Faulty_Solar_Modules |
| TBA |
|
Supported Parameters (RS485)
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Serial-1 | TBA | |
Total_Output_KWH | Rectifier_X.Total Load Energy [KWH] |
|
Solar_KWH | Rectifier_X.Solar_Total_Power [KWH] |
|
Rectifier_Current | Rectifier_X.I_Rectifier | |
Battery_Temperature | Rectifier_X.Temperature_Battery [Celsius] | |
Current | Rectifier_X.I_Load | |
Voltage | Rectifier_X.U_System [V] | |
Battery_SOC_Percentage | Rectifier_X.State_Of_Charge | |
Digital_Inputs | TBA | |
Digital_Outputs | TBA | |
Solar_Curent | Rectifier_X.Solar_Current [A] |