Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Galooli supports a variety of AC meters and Current Transformer Rings according to the changing needs of the users, different currents, amount of phases, conversion ratio, and the diameter of the AC cables.

The meters can include an entry for the AC cable or meters that require the use of Current Transformer Rings.

Current Transformer Rings can be used with cables of varying diameters, some of which have an open and close mechanism.

Info

Read more:
AC Meters:
https://galooli.atlassian.net/wiki/spaces/KP/pages/2429617354/CE+Transducer+CE42?atlOrigin=eyJpIjoiMDE1ODc5ZTM0ZWZmNGZhMzhlZmU0OGY1MTYyOTdmNjUiLCJwIjoiYyJ9
CE Transducer CE42CT
Carlo Gavazzi EM210

AC Current Transformer Rings:
CEhttps://galooli.atlassian.net/wiki/spaces/KP/pages/2441969800/AC+Current+Transformer+Rings+CT#CE-CTH-Split Core
Rogowski -Core%5BhardBreak%5D
https://galooli.atlassian.net/wiki/spaces/KP/pages/2441969800/AC+Current+Transformer+Rings+CT#Rogowski-CT

Which AC meters are suitable for which Current Transformer Rings?

(tick) CE Transducer CE42 AC meter works without any Current Transformer Ring however, the cable entry
can
be too narrow for some cable's diameter.

(tick) CE Transducer CE42CT AC meter works best with theCEhttps://galooli.atlassian.net/wiki/spaces/KP/pages/2441969800/AC+Current+Transformer+Rings+CT#CE-CTH-Split Core-Core%5BhardBreak%5Drings. Specifically with the rings
that has a conversion ratio of 1A.

(tick) Carlo Gavazzi EM210 AC meter works best with the Rogowski https://galooli.atlassian.net/wiki/spaces/KP/pages/2441969800/AC+Current+Transformer+Rings+CT#Rogowski-CT rings.

How to choose the accurate AC Meter and Current Transformer Ring for my site?

...

  • What is the current that needs to be measured?

  • How many phases does the energy source have?

  • What is the conversion ratio?

  • What is the diameter of a cable that needs to be measured?

    The following table allows you to easily choose the required products.
    Catalog numbers are internal to Galooli.

Ring Diameter/Current

≤ 30A

≤ 50A

≤ 150A

≤ 200A

≤ 4000A


≤ 11 mm

CE Transducer CE42

400-ACMetAJ42B-502

No Current Transformer Ring needed


(error)


≤ 24 mm

CE Transducer CE42CT

400-ACMetCE42CT-502

+
CE-CTH


400-AcRin24H30A1A-502CE42CT
400-ACMetCE42CT-502

Split Core (24mm/30A)

CE Transducer CE42CT
+
CE-CTH


400-AcRin24H50A1A-502CE42CT
400-ACMetCE42CT-502

Split Core (24mm/50A)

CE Transducer CE42CT
+
CE-CTH


400-AcRin24H150A1A-502

Split Core (24mm/150A)


(error)


(error)


≤ 36 mm

CE42CT
400-ACMetCE42CT-502

CE Transducer CE42CT
+
CE-CTH


400-AcRin36H30A1A-502CE42CT
400-ACMetCE42CT-502

Split Core (36mm/30A)

CE Transducer CE42CT
+
CE-CTH


400-AcRin36H50A1A-502CE42CT
400-ACMetCE42CT-502

Split Core (36mm/50A)

CE Transducer CE42CT
+
CE-CTH


400-AcRin36H150A1A-502

Split Core (36mm/150A)


(error)


(error)


≤ 350 mm

Carlo Gavazzi EM210


400-EM210HICU-502


+
Rogowski


400-AcRog350-502

CT (350mm)


≤ 600 mm

Carlo Gavazzi EM210


400-EM210HICU-502


+
Rogowski


400-AcRog600-502

CT (600mm)


≤ 900 mm

Carlo Gavazzi EM210


400-EM210HICU-502


+
Rogowski


400-AcRog900-502

CT (900mm)

How accurate are the AC Meter and the AC ring?

Item Codes/Data

Meter
Accuracy

Ring
Accuracy

Accuracy
Calculation

Galooli Item Code

Voltage reading
accuracy

Current reading
accuracy

CT
Accuracy

Overall voltage
accuracy

*Overall current accuracy

*Overall kwh
accuracy

400-ACMetCE42CT-502

CE Transducer CE42CT (Meter)

0.50%

0.50%

Not relevant

400-AcRin24H30A1A-502

CE-CTH Split Core 24mm/30A (Ring)

0.50%

0.50%

0

1.

50%

00%

0.50%

1.

00%

50%

1

2.

50%

60%

400-AcRin24H50A1A-502

CE-CTH Split Core 24mm/50A (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1

2.

50%

10%

400-AcRin24H150A1A-502

CE-CTH Split Core 24mm/150A (Ring)

0.50%

0.50%

1

0.

00%

50%

0.50%

1.

50%

00%

2

1.

00%

50%

400-AcRin36H30A1A-502

CE-CTH Split Core 36mm/30A (Ring)

0.50%

0.50%

0

1.

50%

00%

0.50%

1.

00%

50%

1

2.

50%

60%

400-AcRin36H50A1A-502

CE-CTH Split Core 36mm/50A (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1

2.

50%

10%

400-AcRin36H150A1A-502

CE-CTH Split Core 36mm/150A (Ring)

0.50%

0.50%

1

0.

00%

50%

0.50%

1.

50%

00%

2

1.

00%

50%

**

400-ACMetAJ42B-502

CE Transducer CE42 (Meter)

0.50%

0.50%

Not relevant

1.00%

***400-AcRin150A5A-502 (Ring)

0.50%

0.50%

1.00%

0.50%

1.50%

2.00%

***400-AcRin50A5A-502 (Ring)

0.50%

0.50%

3.00%

0.50%

3.50%

4.00%


*Overall current accuracy = Meter current reading accuracy + CT Accuracy

*Overall kwh accuracy = Overall voltage accuracy + Overall current accuracy

**The meter can measure current and voltage without a CT ring

...