Critical | Urgent | Non Urgent | Observation |
---|---|---|---|
"Circuit breaker alarm" | "CLD active indicator" | "Charge stop indicator", | |
"Anti-theft alarm" | "Balanced cells indicator" | ||
"Short-circuit alarm" | "Non-quiescent state indicator" | ||
"Over-current discharge alarm" | "Charge stop ready indicator" | ||
"Over-temperature alarm" | |||
"Under-voltage alarm" | |||
"Over-voltage alarm" | |||
"Discharge blocked alarm" | |||
"Under-temperature alarm" | |||
"Over-current charge alarm" | |||
"Charge blocked alarm" |
Supported Parameters
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Battery SOC Percentage | Smart_Battery_X.SOC | |
Battery SOH | Smart_Battery_X.SOH | |
Voltage | Smart_Battery_X.Voltage [V] | |
Current | Smart_Battery_X.Current [A] | |
Cell Voltage Min | Smart_Battery_X.Cell_Voltage_Min [V] | |
Cell Voltage Max | Smart_Battery_X.Cell_Voltage_Max [V] | |
Temperature 1-3 | Smart_Battery_X.Temperature_1-3 [Celsius] | Temperature 1 - cell temperature Temperature 2 - cell temperature Since lithium batteries are prone to catching fire and exploding at high temperatures, there are two temperature meters for the same purpose. Temperature 3 - FET temperature |
Battery Cycles | Smart_Battery_X.Cycles |
Polarium (SNMP)
By utilizing the rectifier (currently supported by Delta and CFX) the information from the Polarium smart batteries can be read via SNMP.
...
Communication Method
SNMP (Ethernet). Currently, the data is read through a Delta and SFX rectifier, rather than a direct connection to the batteries.
Wiring Diagram
Same as RS485 (Modbus) - Polarium (Modbus)
Network Configuration
The batteries are configured in the Power Center via SNMP ETH Devices, since the readings come from the rectifier.
...
Device IP | 192.168.70.2 | Device ID
---|
Version Update
Same as RS485 (Modbus) - Polarium (Modbus)
...
Configuration Process
...
Same as RS485 (Modbus) - Polarium (Modbus)
...
Alarms List
To be announced