Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

This feature is available only to organizations with a Platinum license.

The X-Ray Accuracy is part of the Galooli Manager Application, it provides a visual representation of how the organization is performing in relation to its predetermined configurations and thresholds.

...

The accuracy display provide and overview of the validity of the user's settings. The user will be able to choose different X-RAY parameters (e.g., VPMG, float voltage, etc.) and to apply different filters (e.g., battery type, rectifier type, communication node).

Table of Contents

...

X-Ray

...

Dashboard Display

Here, you will find a dashboard with various cards that display the validity of settings as well as a settings history that shows the history of settings over time.

  • No. of Sites - The number of sites within the organization

  • Total Sites with Invalid Configurations - Number of sites with invalid configurations

  • Total Invalid Configurations - Total number of invalid configurations that need to be corrected

  • Configuration Pie Charts - Each pie chart represents an a specific X-Ray item that is being monitored by the organization:

    • The green slices indicate the number of sites with the configuration in the correct value

    • The red slice indicates how many sites have an invalid configuration

    • The grey slice indicates how many sites are not supporting the specific configuration, so it is not relevant for them

    • The orange slice indicates the number of sites with parameters that the X-ray tool is supposed to be able to read, but is unable to do so for some reason. In terms of the X-ray management, "active" is true, but the "actual value" is empty.

       

Clicking on a specific configuration item on the green or red slices will cause all the data on the screen to be changed in accordance with that item.

Re-click the marked pie section to remove the filter.

...

X-Ray Filtration Tools

There are filter options on the top of the screen that enable the user to focus on sites that have a particular type of device or layout. The user can also change the X-ray items (charts) that appear on the dashboard.

  • Selected Units - A selection of units from the organization tree, excluding the cluster “STOCK”. The default choice will be the entire organization.

  • Advanced Filter - An advanced filtering tool that allows the user to filter the information according to different devices and models

  • +Charts - The tool allows the user to select which configurations to display. The number of pies in the dashboard is directly affected by this filter

...

Selected Units

Advanced Filter

+Charts

Image Removed
Image Added

 

Image Modified

 

Image Modified

 

X-Ray Accuracy Report

The purpose of the Accuracy Report is to identify the specific sites with the configuration issues.

In the accuracy report, the data displayed in the dashboard is represented in a table format. As a result, the table's columns include the selected filters and configurations. The table will only display units that are included in the dashboard (and were not filtered out by the filters or pie charts).

After issuance, the report can be filtered and exported to CSV/Excel.

...

Default Settings For Parameters

In case the organization does not configure the min, max, and set values via the X-Ray Management, the basic data will then be displayed by Galooli. The basic data will be based on internal Galooli default values and thresholds.

Info

The internal default values are set just to avoid leaving the display empty for new users. It is strongly recommended to configure your own values.

Name

Min Valid Value

Max Valid Value

Set Value

X-RAY.Rectifier-1-5. DG Off Voltage

56.3

57

56.3

X-RAY.Rectifier-1-5. DG Off Voltage 2

56.3

57

56.3

X-RAY.Rectifier-1-5. DG On Voltage

46.5

50.9

46.5

X-RAY.Rectifier-1-5. Event Controlled Charge Voltage

43.5

57.6

43.5

X-RAY.Rectifier-1-5. Battery Float Voltage

53

57.2

53

X-RAY.Rectifier-1-5.
LVD

42

46.9

42

X-RAY.Rectifier-1-5. Power Up Time

30

320

60

X-RAY.Rectifier-1-5. Temp Compensation Enable

Yes

Yes

Yes

X-RAY.Rectifier-1-5 VPMG Voltage

0.5

1.0

0.8

X-RAY.Rectifier-1-5. Rectifier Float Voltage

53

57.2

57.2

X-RAY.Rectifier-1-5. Solar Float Voltage

53

57.2

57.2