Open the PowerCenter (if the power center was already open, close, and re-open it).
Open the “Active Device” drop-down menu and select “Elara”.
Open the “Connect Via” drop-down menu and select the relevant Serial COM port.
...
4. Navigate to the “Elara” tab.
...
5. Navigate to the “Configuration” tab
6. Click the “Read Configuration” button.
...
7. Click the “Add Port 1 Device” in the Configure tab.
...
8. The “Elara – Modbus Device Configuration” window will pop up
a. In the first “Device” dropdown list, select the “Fuel_Meter” option.
b. In the second “Device” dropdown list, select “HolykellHPT604” option
c. Input the “Physical and Virtual device ID” according to your wiring diagram.
d. In “Device baud rate”, select “19200”
e. Click “Apply”.
...
9. Click the “Write Configuration” button to save the changes.
...
10. Click the “Reset” button.
...
After the PowerCenter configuration process, ensure the sensor provides a connected indication and that the “N value” is close to zero.
Please note! A suitable error rate in an ambient atmosphere is between +7 and –7 [N value]. If this happens, then go to Sensor Initial Configuration step 8e.
...