Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Image Added
Image Added

Image Added

Supported Models

...

DSE 7320

Model

Communication Method

DSE

...

7320

...




RS485

DSE

...

DSE 4510

...

7450 Battery Plant

DSE 7320 MKII

DSE

...

7410 MKII

DSE

...

DSE 6620

...

DSE 6120

...

DSE 4521

...

DSE 7410 MKII

...

8610 MKII -

View file
nameDSE8610-MKII-Data-Sheet-(US).pdf

DSE 6620

DSE857 adapter extension is needed.
Please make contact with your supplier and Galooli support team

...

https://galooli.atlassian.net/l/cp/v1duJaCC

DSE 4521

DSE 4520

DSE 6610

DSE 4510

DSE 6120

DSE 6110

DSE 6012

DSE 6020

DSE 6010

DSE 7220

Network configuration

Device Baudrate

19200

...

Device Configuration

...

Supported Services

Parameters

Alarm Name

Alarm Criticality

Remote Controlling

Engine_Hours

low oil pressure

critical












Supported in all models

Grid_Voltage_Phase_1-3

emergency stop

critical

Battery_Voltage

low coolant

observation

Engine_Speed

high coolant

urgent

Frequency

over speed

urgent

Voltage_Phase_1-3

under speed

urgent

Current_Phase_1-3

over freq.

urgent

Coolant_Temperature

under freq.

urgent

Oil_Pressure

high voltage

urgent

Working_Mode

low voltage

urgent

Total_Output_KWH

high battery

urgent

low battery

urgent

fail to start

critical

alternator fail

urgent

fail to close

observation

fail to stop

urgent

Child pages (Children Display)