Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Field Name

Field Description

Calculation Method

Rectifier X Load Energy Initial [KWH]

The first record of the kWh value that was read from the rectifier, for the selected time range. 

Rectifier X Load Energy Final [KWH]

The last record of the kWh value that was read from the rectifier, for the selected time range.

Rectifier X Load Energy Total [KWH]

The total energy (kWh) that was converted by the rectifier, for the selected time range.

Rectifier X Solar Initial [KWH]

The first record of the solar kWh value was read from the rectifier, for the selected time range.

Rectifier X Solar Final [KWH]

The last record of the solar kWh value was read from the rectifier, for the selected time range.






Rectifier X Solar Total [KWH]


The total solar production (kWh) for the selected time range, as read from the rectifier.

The kWh difference between 2 subsequent records will be aggregated if the following are true:

  1. The difference is positive. 

  2. Compare the current record to the last valid record

  • If the time difference > 60min > the extrapolation of the value for the total kWh of the day is less than 300 kWh.

  • Otherwise, the extrapolation of the value for the total kWh of the day is less than 3000 10,000 kWh.

Rectifier X - V Min/Max/Avg* [V]

The maximum, minimum, and average DC voltage of the site, as read from the rectifier.

Rectifier X - Battery I Min/Max/Avg* [A]

The maximum, minimum, and average current of the battery, as read from the rectifier.


Rectifier X - I Input avg* [A]


The average of the rectifier's battery current measurement and load current measurement.

The average of Rectifier_X.I_Load + Rectifier_X.I_Battery. The value is aggregated if it is larger than 5A and smaller than 250A.

Rectifier X - Battery charging I avg* [A]

The average current that was used to charge the batteries, as read from the rectifier.

Rectifier X - Min/Max/Avg* Load Current [A]

The maximum, minimum, and average current of the rectifier's load output.

Rectifier X - Min/Max/Avg* Internal Temp [Celsius]

The maximum, minimum, and average internal temp of the rectifier.

Rectifier X - Min/Max/Avg* Batt. Temp [Celsius]

The maximum, minimum, and average internal temp of the battery.

This field based on the analog detailed field "Rectifier_X.Temperature_Battery [Celsius]".

Rectifier X - Max Solar Cell Power [W]

The maximum solar power that was supplied in the selected time range was read from the rectifier.

Rectifier X - Min/Max/Avg* Ambient Temp [Celsius]

The maximum, minimum, and average ambient temperature.

SOLAR_Module X V Max/Avg* [V]

The maximum and average voltage of the solar module for the selected time range.

Based on the detailed fields Rectifier_Y.Solar_Voltage_X [V]

X=1->4, Y=1->5

SOLAR_Module X I Max/Avg* [A]

The maximum and average current of the solar module for the selected time range.

Based on the detailed fields Rectifier_X.Solar_Current_X [V]

X=1->4, Y=1->5

Rectifier X - Communicating Solar Modules Max

Maximum number of modules that communicate with the rectifier.

Rectifier X - Communicating Rectifier Modules Max

*Zeros are ignored in the calculation of averaged fields