Device Baudrate | 19200 |
---|---|
Device ID | All modules share the same master device ID (usually 0x01). see Galooli configuration tool for module detailes |
Alarms List
Critical | Urgent | Non Urgent | Observation |
---|---|---|---|
"Cell Over Voltage Fault 2" | "Cell Over Voltage Fault 1" | "Cell Over Voltage Warning" | "Cell Over Voltage Alarm" |
"Cell Under Voltage Fault 2" | "Cell Under Voltage Fault 1" | "Cell Under Voltage Warning" | "Cell Under Voltage Alarm" |
"Over Charging Current Fault 2" | "Over Charging Current Fault 1" | "Over Charging Current Warning" | "Over Charging Current Alarm" |
"Over Discharging Current Fault 2" | "Over Discharging Current Fault 1" | "Over Discharging Current Warning" | "Over Discharging Current Alarm" |
"Available charge limit over Fault 2" | "Over Temperature Fault 1" | "Over Temperature Warning" | "Over Temperature Alarm" |
"Available discharge limit over Fault 2" | "Under Temperature Fault 1" | "Under Temperature Warning" | "Under Temperature Alarm" |
"Over Temperature Fault 2" | "Cell Voltage Difference Fault 1" | "Cell Voltage Difference Warning" | "Over SOC Alarm" |
"Under Temperature Fault 2" | "Module Temp Difference Fault 1" | "Available charge limit over Warning" | "Under SOC Alarm" |
"Internal Communication Fault 2" | "Available charge limit over Fault 1" | "Available discharge limit over Warning" | "Module Temp Difference Alarm" |
"Pack Under Voltage Fault2" | "Available discharge limit over Fault 1" | "Under SOC Warning" | "Available charge limit over Alarm" |
"BMS HW Fault 2" | "Internal Communication Fault 1" | "Over SOC Warning" | "Available discharge limit over Alarm" |
"External Communication Fault 1" | "Under SOH Alarm" |
Supported Parameters
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Battery_SOC_Percentage | Smart_Battery_X.SOC | |
Battery_SOH | Smart_Battery_X.SOH |
|
Voltage | Smart_Battery_X.Voltage [V] |
|
Current | Smart_Battery_X.Current [A] |
|
Cell_Voltage_Min | Smart_Battery_X.Cell_Voltage_Min [V] |
|
Cell_Voltage_Max | Smart_Battery_X.Cell_Voltage_Max [V] |
|
Temperature_1-2 |
Smart_Battery_X.Temperature_X[Celsius] | Temperature 1 - cell temperature Temperature 2 - cell temperature Since lithium batteries are prone to catching fire and exploding at high temperatures, there are two temperature meters for the same purpose. |
Battery_Cycles | Smart_Battery_X.Cycles |
|