Supported Models
...
CH48150
Manufacturer site - https://en.changhongbatteries.com/
Communication Method
RS485 connection
Wiring Diagram
...
Pinout | RJ45 side ports |
1 or 8 | RS485 B |
2 or 7 | RS485 A |
...
Network Configuration
Device Baudrate | 9600 |
---|
...
For configuring the physical ID when there are one or more batteries connected to one another, the following actions must be taken. As shown in the table, the "ADD" part must be configured according to the number of batteries, on each battery separately.
...
Add a serial device in Power Center >> Choose "Smart Battery" >> "Changhong" >> Set the "Physical Device ID" and "Virtual Device ID" as follows and according to the number of batteries:
Number Of Batteries | Physical Device ID | Virtual Device ID |
---|---|---|
1 | 1 | 70 |
2 | 2 | 71 |
3 | 3 | 72 |
4 | 4 | 73 |
Supported Parameters
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Current | Smart_Battery_X.Current [A] | |
Voltage | Smart_Battery_X.Voltage [V] | |
Battery_SOC_Percentage | Smart_Battery_X.SOC | |
Battery_SOH | Smart_Battery_X.SOH | |
Battery_Cycles | Smart_Battery_X.Cycles | |
Temperature_1 | Smart_Battery_X.Temperature_X[Celsius] |
Manufacturer Data
View file | ||
---|---|---|
|
View file | ||
---|---|---|
|