Site Global

Field Name

Field Description

Calculation Method

Site Global AC Tenants Load Power [W] 

Summary of the Tenant_X.Power fields when the tenant is configured (Tenant_X.Configured = True) and the AC Meter is not configured for the tenant (TenantX.AC_Meter = False).

Note: The field included all tenants who met the criteria above

Site Global DC Tenants Load Power [W]

Summary of the Tenant_X.Power fields when the tenant is configured (Tenant_X.Configured = True) and the AC Meter is not configured for the tenant (TenantX.AC_Meter = False).

Note: The field included all tenants who met the criteria above

Rectifier

Field Name

Field Description

Calculation Method

Rectifier_X.Communication_Rectifier_Modules

This field indicates the number of modules that are actually communicating with the rectifier. As an example, on a specific site there may be five solar modules that produce X [KW], but only three of them transmit information to the rectifier, so the value reported in the report is smaller than the actual value produced. These fields will enable to investigate the exception.

Rectifier_X.Communication_Solar_Modules

Rectifier_X.Total_Load_Energy [KWH]

 

Rectifier_X.Used_Capacity

Calculation of the load percentage on a rectifier in relation to its capacity.

 Rectifier_X.Used_Capacity will only provide results to customers for whom the X-Ray is active (in particular, platinum licensees).

100 * ([Rectifier_1.U_System [V]] * [Rectifier_1.I_Rectifier [A]]) / ([Rectifier_1.Communication_Rectifier_Modules] * 2900)