Field Name | Field Description | Calculation Method |
---|---|---|
Avail. Time Grid | Total time (hours) the grid was available | Based on records where Site_Global.Grid_Available = Yes. At the end of the document, there are comments regarding availability. |
Avail. Time Grid - Fully Available | Total time (hours) the when all grid phases configured for the unit were available. | Based on records during which all phases configured for the unit are available. At the end of the document, there are comments regarding availability. |
Avail. Time Generator X | Total time (hours) generator 1 was running. | Based on records where Site_Global.Generator X_Running = Yes. At the end of the document, there are comments regarding availability. |
Avail. Time Solar | Total time (hours) the solar supplied power which was greater than 0W to the site. | Based on records where one of the fields Rectifier_X.Solar Power [W] was greater than 0. At the end of the document, there are comments regarding availability. |
Usage Time Grid | The total time (hours) the grid was contributing to the site's load. This is the time the grid was on load, multiplied by the part load it supplied (between 0-100%). | Based on records where Site_Global_Grid_On_Load = Yes, multiplied by the value of Site_Global_Grid_Load [%]. At the end of the document, there are comments regarding availability. |
Usage Time Generator X | The total time (hours) generator X was contributing to the site's load. This is the time the generator was on load, multiplied by the part load it supplied (between 0-100%). | Based on records where Site_Global_GeneratorX_On_Load = Yes, multiplied by the value of Site_Global_GeneratorX_Load [%]. At the end of the document, there are comments regarding availability. |
Usage Time Solar | The total time (hours) the solar was contributing to the site's load. This is the time the solar was on load, multiplied by the part load it supplied (between 0-100%). | Based on records where Site_Global_Solar_On_Load = Yes, multiplied by the value of Site_Global_Solar_Load [%]. At the end of the document, there are comments regarding availability. |
Usage Time Battery | The total time (hours) the battery was contributing to the site's load. This is the time the battery was on load, multiplied by the part load it supplied (between 0-100%). | Based on records where Site_Global_Battery_On_Load = Yes, multiplied by the value of Site_Global_Battery_Load [%]. At the end of the document, there are comments regarding availability. |
Usage Time Unknown | The total time (hours) an unknown source was contributing to the site's load. This is the time the unknown source was on load, multiplied by the part load it supplied (between 0-100%). | Based on records where Site_Global_Unknown_On_Load = Yes, multiplied by the value of Site_Global_Unknown_Load [%]. At the end of the document, there are comments regarding availability. |
| The total time there was an active PLD or LVD alarm, and the rectifier's current was less than a half the average current of the rectifier in the previous day. | Based on the records where Site_Global.DC_Status_PLD = Yes or Site_Global.DC_Status_LVD = Yes, and Rectifier_1.I_Load [A] At the end of the document, there are comments regarding availability. |
Grid Initial Credit Balance | The grid credit balance of the first day in the selected time range. | If the additional information field “Balance Update Date” is the date the report was executed on, the initial credit balance will be equal to the additional information field “Balance kWh”. |
|
| The grid initial credit balance minus the energy from the grid that was supplied to the site (Grid Total kWh). The data source for the grid kWh can be the grid AC meter or the ATS AC meter. |
|
| The estimation is done by estimating the energy consumption from the grid to the site. The estimated consumption is determined by the maximum value between the grid kWh supplied to the site on the previous day, to the average value of the grid kWh supplied to the site on the last 7 days. |
Grid ph1..3 V Max/Min/Avg | The minimum, maximum, and average voltage of the grid phase for the selected time range. The | Based on Site_Global.Grid_V1..3 |
Grid ph1..3 A Max/Min/Avg | The minimum, maximum and average current of the grid phase for the selected time range. | Based on Site_Global.Grid_I1..3 |
Grid ph1..3 Power Factor Max/Min | The minimum and maximum power factor of the grid phase for the selected time range | |
Grid - Power Max/Min/Avg [kW] | The minimum, maximum and average power from the grid in the selected time range. | Based on Site_Global.Grid_Power. |
Grid - Total Energy Peak Hours [KWH] | In a peak period, the grid tariff is the highest due to the high level of demand from the grid customers |
|
Grid - Total Energy Off-Peak Hours [KWH] | During off-peak hours, when grid customers' demand is low, the grid tariff is the least expensive | |
Grid – Total Energy Shoulder Hours [KWH] | Any time other than peak or off-peak hours | |
| Total energy supplied from the site to the grid. The data this field is based on can be the grid AC meter or ATS AC meter. | Same implementation as the "Grid - Total Energy", but aggregate the kW*dt only if for the first record Site_Global.Grid_Power < 0 |
Solar - Power Max/Min/Avg [kW] - | The minimum, maximum and average power produced from the solar in the selected time range. | Based on Site_Global.Solar_Power. |
Battery - Power Max/Min/Avg [kW] | The minimum, maximum and average power of the battery in the selected time range. | Based on Site_Global.Battery_Power |
| The minimum, maximum and average power consumption of the site in the selected time range. The consumers’ load is the maximum value between the rectifiers’ power and the tenants’ power, in addition to the power consumed by the cooling systems (1-4). | based on Site_Global.Consumers_Load_Power |
Sources Load - Power Max/Min/Avg [kW] | The minimum, maximum and average power supplied by the energy sources of the site in the selected time range. It is a summation of the grid power, generators power, and solar power/ | Based on Site_Global.Sources_Load_Power |
Generator X - Load Power Max/Min/Avg [kW] | The minimum, maximum and average power produced from the generator in the selected time range. | Based on Site_Global.Generator1/2_Load_Power. |
| Total solar energy that was produced in the selected time range. The solar data source can be any of the follows: Solar meters, solar inverters or charge controllers, rectifiers. | Based on Site_Global.Solar_Power. At the end of the document, there are comments regarding availability. |
Consumers - Total Energy [kWh] | Total energy consumption of the site in the selected time range. The energy consumption is determined by the rectifiers/tenants, in addition to the cooling systems. | Based on Site_Global.Consumers_Load_Power. At the end of the document, there are comments regarding availability |
Sources - Total Energy [kWh] | Total energy supply to the site by the energy sources, including the grid, solar and generators. | Based on Site_Global.Sources_Load_Power At the end of the document, there are comments regarding availability |
Grid - Total Energy [kWh] | Total energy supplied from the grid to the site. The data this field is based on can be the grid AC meter or ATS AC meter. | Based on Site_Global.Grid_Power. At the end of the document, there are comments regarding availability |
Generator X - Total Energy [kWh] | The data this field is based on can be the generator’s panel, generator AC meter or ATS AC meter. | Based on Site_Global.Generator1/2_Load_Power. |
Battery – Total Discharge [kWh] | Total energy (kWh) supplied to the site from the discharge of the batteries on site. | Based on the fields Site_Global.Battery_Power. The battery discharge state is determined by the field Site_Global.Battery_Discharging. |
Battery - Total Charge [kWh] | Total Energy used to charge the batteries on site. | Based on the fields Site_Global.Battery_Power. The battery charge state is determined by the field Site_Global.Battery_Charging. |
Wind – Total Energy [kWh] | Total energy produced from wind in the selected time range. | The data source is the inverters' wind power data. Based on Site_Global.Wind_Power. |
Wind Power Max/Avg | The maximum and average power produced from the wind in the selected time range | |
DC Tenants Load - Power Max/Min/Avg [kW] | The max/min/avg of 'Site Global DC Tenants Load Power' divided by 1000 | |
DC Tenants Load - Total Energy [kWh] | Same as Consumers - Total Energy implementation, but using 'Site Global DC Tenants Load Power' | |
AC Tenants Load - Power Max/Min/Avg [kW] | The max/min/avg of 'Site Global AC Tenants Load Power' divided by 1000 | |
AC Tenants Load - Total Energy [kWh] | Same as Consumers - Total Energy implementation, but using 'Site Global AC Tenants Load Power' |
The availability time is calculated by accumulating the time between records where the relevant asset was connected. The time will be accumulated only if the time difference between the subsequent records is less than 15** minutes. In addition, if the calculated availability value is larger than the Data Availability value, the value will be assigned to the Data Availability value.
...