Hardware Specification

General specifications

Power Supply

6 - 16 V

Power Consumption

Storage mode ~25uA

In Cabinet mode ~25uA

Daily report mode (MODEM Only) ~35mA

Tracking mode (MODEM+GPS) ~50mA

GSM/GPRS

Internal Antenna

LTE Cat M1/Cat NB1/EGPRS

GNSS

Antenna type - Internal

GNSS Systems 99 acquisition channels
33 tracking channels
GPS Support
GLONASS Support

Sensitivity -167 dBm

Time To First Fix (90% @ -130 dBm) - Cold Start: ‹ 35 s

Serial Communication

RS485

Memory logger

10000 messages (Aprox.)

Storage Temperature

-40 - 85 Celsius

Working Temperature

-20 - 70 Celsius

Max. Relative humidity

90%

Weight

34 g (Aprox.)

Size

41x86 mm
Height: 10.3mm

Movement detection

Number of Axis

3

Full scale

+-2g

Sampling rate

50Hz

Movement detection threshold

0.25g

Voltage Measurement

Max voltage

19v

Resolution

0.01v

Accuracy

0.05v

Temperature sensor

Sensor type

NTC

Range

[5,50] Celsius

Resolution

0.01 Celsius

Accuracy

1 Celsius

Pinout

...

Power

Pin #

Name

1

V+

2

V+ (not in use)

3

V- (not in use)

4

V-

RS485

Pin #

Name

1

RS485-A

2

RS485-B

3

GND

Status LEDs

The LEDs status depends on the type of modem:

...

Status is set by the unit itself.

Sparta Status Logic

The Sparta mods and the status in ZonMax are linked to facilitate the process of creating an alert.

...

 

Mode

...

ZonMax Status

...

Maintenance

...

Idle

...

In Cabinet

...

Off

...

 

Tracking

...

On, Stop, Moving

Like all other systems, depends on the speed

Events

Users can generate events in the system and link the mode to the status.

...

It may be necessary to manually configure the Sparta GPS location if there is no cellular GPS reception in a particular location.

Please follow the next steps in order to set the Sparta location manually:

  1. Connect the computer to the Sparta gateway.

  2. Open the Power Center (if the Power Cent was already open, close it, and re-open it).

  3. Open the “Active Device” drop-down menu and select “Power Device”.

  4. Open the “Connect Via” drop-down menu and select the “OTASerial” connection.

...

  1. Provide the relevant login parameters and your Sparta ID.

  2. To set the location manually the Sparta should be in “Maintenance” mode. In order to switch to this mode navigate to the "Sparta" tab and click on “Maintenance Mode”. Please approve the pop-up.

...

Lead Acid Battery Compliance For Sparta

Northstar

Enersys

Fiamm

Sacred Sun

NSB (150-210)FT

PowerSafe SBS (100-190)F

12 FIT 101

FTA12-100

 

PowerSafe V-FT (100-190)

12 FIT 100/23

FTA12-150 

 

 

12 FIT 150

FTA12-200

 

 

12 FIT 180

 

 

 

12 FIT 201

 

 

 

12 FHT 101

 

 

 

12c FHT 181

 

 

 

12 FHC 95

 

 

 

12 FHC 175 

 

 

 

12 FLB 700

 

Installation Video

 https://www.youtube.com/watch?v=rNIjyaI3Un0&list=PL6jYON57NnXzHbXYUB9yWl-O61sHv_GPd&index=4&ab_channel=Galooli

...