Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Table of Contents
stylenone

Supported Models

Communication Methods

Read/Write Community

Eltek_SmartPack

RS485

Not Relevant


Eltek_SmartPack2


RS485/SNMP

Read - public
Write - v1private

Eltek_SmartPack2Touch

SNMP

Read - v1community
Write - v1private

Eltek_SmartPackS

SNMP

Network

...

Configuration for ETHERNET/SNMP

...

Connection

Device IP

 192.168.10.20

Subnet mask

 255.255.255.0

Gateway

 192.168.10.1

Host IP (Web/Elara configuration)

 192.168.10.21

Network

...

Configuration for RS485

...

Connection

Device Baudrate

 19200

RS485 Wiring

...

Diagram

...

SmartPack

...

Configuration

Username - admin
Password - admin

...

SmartPack2

...

Configuration

...

Smart_Pack2 Touch

...

Configuration

...

SmartPack2 & S Touch SNMP Configuration

The following steps should be taken as soon as you receive your new “SmartPack 2 and S Touch Rectifier”:

1. In order to activate the SNMP option after installation, login to the rectifier controller and copy your
specific MAC address.

...


2. You will need to contact a representative from "Eltek" to activate the SNMP feature; you will need to
provide the MAC address from the previous paragraph and ask for a "license key.”

3. Once the "license key" has been reserved from "Eltek", enter it and proceed to the next step.

...


4. Check the “Web-based configuration” to enable the web SNMP configuration.

...

  1. SNMP is now available